HYDRAR15-E2401M HYDRAR18-E2401M HYDRAR20-E2401M HYDRAR24-E2401M HYDRAR27-E2401M HYDRAR29-E2401M Manufactured by: Dettson Industries Inc 3400, Industrial Boulevard Sherbrooke, Qc, Canada, J1L 1V8 www.dettson.ca INSTALLER / SERVICE TECHNICIAN : Attention Use the information in this manual for the installation / servicing of the boiler and keep the document near the unit for future reference.
TABLE DES MATIÈRES INDEX DES TABLEAUX Table 1. Minimum clearances to combustible materials..4 Table 2. Hydra Revolution – Technical specifications...12 SECTION 1 INSTALLATION ........3 Table 3. Parts list ............18 Table 4. Parts list ............20 DANGER, WARNING AND CAUTION ....3 HEATING WITH HOT WATER ......
SECTION 1 INSTALLATION DANGER, WARNING AND CAUTION INSTALLATION The words DANGER, WARNING and CAUTION are used to identify WARNING the levels of seriousness of certain hazards. It is important that you understand their meaning. You will notice these words in the manual The installation of this unit must be performed as follows: by a qualified technician and it must conform...
Figure 1: Mounting configurations *The arrows represent the direction of the water flow CLEARANCES DISTRIBUTION SYSTEM The following clearances should be provided for the servicing of the The proper functioning of your heating system is directly related to unit: the quality of the plumbing installation. Therefore, the entire installation must be performed by qualified technicians.
Figure 2: Boiler components Element Drain Valve, if required ¼" High Limit Sensor Water Sensor T° Thermodisc Protector Relay Element Rectifier Card Manometer High Limit Circuit Breaker 208/240VAC – 24VAC Transformator Power Card Regulator Terminal Block Freeze protection (when required) All installations must include the following items: 1 pressure regulator, adjusted to 12 psi, must be installed WARNING...
1.8.1 Connecting the Circulating Pump INSTALLATION OF THE BOILER Connect the circulating pump on 120V connections points identified At the time of installation, the following steps should be followed. N for neutral and P for controlled 120V output in the control panel as Refer to Figure 5,6,7,8 and 9.
SECTION 2 OPERATION Consumption: 2 ADJUSTMENTS AND START-UP The consumption menu shows an approximated value of the power consumed by the boiler since it was last reset. CAUTION Consumption is written in kilowatt The boiler must be filled with water and all air hour and time since last reset is given in hours or in days.
Page 8
Under no circumstances should a user try to access it. This function is used at the Dettson T° ext: Allows the device to know if an external factory to test the Hydra Revolution before it sensor is being used.
Figure 5: ODULATION IN FUNCTION OF THE EXTERIOR TEMPERATURE Boiler temperature in function of outside temperature 175,0 165,0 155,0 Plinth (T_Setpoint = 175ºF) 145,0 Cast Iron (T_Setpoint = 150ºF) 135,0 Light (T_Setpoint = 125ºF) Mass (T_Setpoint = 100ºF) 125,0 115,0 105,0 95,0 85,0...
3 SECTION - MAINTENANCE The property owner has the following responsibilities: It is recommended that the boiler be purged annually, in order to eliminate sediment and sludge that may have accumulated at the To maintain the area around the boiler clean at all times and bottom of the boiler and covered the heating elements.
Electrical panel Panel only B04182-01 Triac protector assembly A00421 Ext. sensor electrical wiring F14G007 Card sleeve PC .315 CBDLS525 R99G020 Dettson control 2013 Control only B04205 Electronic wiring L01F010 Transformer 208/240/120 B04184 Aquastat support assembly Aquastat, bottom and support included...
Electrical panel Panel only B04183-01 Triac protector assembly A00421 Ext. sensor electrical wiring F14G007 Card sleeve PC .315 CBDLS525 R99G020 Dettson control 2013 Control only B04206 Electronic kit L01F010 Transformer 208/240/120 Aquastat, bottom and support B04184 Aquastat support assembly included...