Latching Relay (Lt-Clr); Acknowledging Relays; Figure 21. Acknowledge Relays W/Function Key Or Digital Input - Omega DP6060 User Manual

Dual-input process meter
Table of Contents

Advertisement

DP6060 Dual-Input Process Meter

Latching Relay (Lt-Clr)

Manual reset only after alarm condition has cleared
Condition
Normal
Alarm
Ack (No effect)
Normal
Ack
In this application, the meter is set up for manual reset only after the
signal passes the reset point (alarm condition has cleared).
Acknowledging the alarm while it is still present has no effect on either
the LED or the relay. When the alarm is acknowledged after it returns to
the normal state, the LED and the relay go off. Notice that the LED
remains on, even after the meter returns to the normal condition. This is
because, for latching relays, the alarm LED reflects the status of the
relay, regardless of the alarm condition.

Acknowledging Relays

There are two ways to acknowledge relays programmed for manual
reset:
1. Via the programmable front panel function keys F1-F3 (Default:
F3 assigned to ACK).
2. Remotely via a normally open pushbutton wired across one of
the digital inputs and the +5 V terminals on the digital I/O
modules, or using the F4 digital input, which is triggered with a
contact closure to COM, or with an active low signal (see page
26).
When the ACK button or the assigned digital input is closed, all relays
programmed for manual reset are acknowledged.

Figure 21. Acknowledge Relays w/Function Key or Digital Input

LED
Off
On
On
On
Off
DPA1044 Digital I/O Module
1
2
3
4
+5
I1
I2
I3
DI 1-4
ACK
62
Instruction Manual
Relay
Off
On
On
On
Off
5
6
7
8
O1
O2
O3
I4
DO 1-4
9
10
O4
G
GND

Advertisement

Table of Contents
loading

Table of Contents