Remote Controller Setting Range : Code 10
Main Menu &
Code
Remote
Water Out Temp for Cooling
Controller
Setting Range
Room Temp for Cooling
Code 10
Water Out Temp for Heating
Room Temp for heating
DHW Tank Temp
Space Cooling
• Target water outlet temperature : U pper limit(#1011, Default 25ºC, Range : 18 ~ 25ºC),
- With this default FSV settings, user can change the target water outlet temperature within
the range of 5 ~ 25ºC for cooling
• Target room temperature : U pper limit(#1021, Default 30ºC, Range : 24 ~ 30ºC),
- With this default FSV settings, user can change the target room temperature within the
range of 18 ~ 30ºC for cooling.
• T he #1 DIP switch in the wired remote controller should be set to "OFF"(Default) for
cooling operation of heat pump.
• T he #2 DIP switch in the wired remote controller should be set to "OFF"(Default) to
control the water outlet temperature.
• T he #2 DIP switch in the wired remote controller should be set to "ON" to control the
room temperature.
• T he #3 DIP switch in the wired remote controller should be set to "OFF"(Default) to
control the air sensor in remote controller.
• T he #3 DIP switch in the wired remote controller should be set to "ON" to control the
external air sensor.
Space Heating
• Target water outlet temperature : U pper limit(#1031, Default 55ºC, Range : 37 ~ 55ºC),
- With this default FSV settings, user can change the target water outlet temperature within
the range of 25 ~ 55ºC for heating.
• Target room temperature : U pper limit(#1041, Default 30ºC, Range : 24 ~ 30ºC),
- With this default FSV settings, user can change the target room temperature within the
range of 16 ~ 30ºC for heating.
• T he #2 DIP switch in the wired remote controller should be set to "OFF"(Default) to
control the water outlet temperature.
• T he #2 DIP switch in the wired remote controller should be set to "ON" to control the
room temperature.
DHW Heating
• Target DHW tank temperature : U pper limit(#1051, Default 50ºC, Range : 50 ~ 80ºC),
- With this default FSV settings, user can change the target tank temperature within the
range of 40 ~ 50ºC for DHW heating.
The FSV #3011 in the wired remote controller should be set to "1(Yes)" to use DHW
function.
RC120MHXGA_IB_E_34412A(1).indd 33
Field Setting Value
Sub Menu Function
Lower limit(#1012, Default 16ºC, Range : 5 ~ 18ºC)
Lower limit(#1022, Default 18ºC, Range : 18 ~ 22ºC)
Lower limit(#1032, Default 25ºC, Range : 15 ~ 37ºC)
Lower limit(#1042, Default 16ºC, Range : 16 ~ 22ºC)
Lower limit(#1052, Default 40ºC, Range : 30 ~ 40ºC)
Sub
Description
Default
Code
Max
25
11
Min
16
12
Max
30
21
Min
18
22
Max
55
31
Min
25
32
Max
30
41
Min
16
42
Max
50
51
Min
40
52
Operating advanced function _33
Min
Max
Step
Unit
18
25
1
˚C
5
18
1
˚C
24
30
1
˚C
18
22
1
˚C
37
55
1
˚C
15
37
1
˚C
24
30
1
˚C
16
22
1
˚C
50
70
1
˚C
30
40
1
˚C