Samsung Control Unit User Manual page 37

Air to water heat pump -mono control unit
Table of Contents

Advertisement

Main Menu &
Sub Menu Function
Code
DHW Code
Domestic Hot Water
30
Tank
Heat Pump
Booster Heater
Disinfection
Power DHW by User
Input
Solar Panel
Direction of the
valves
DHW Application
The FSV #3011 in the wired remote controller should be set to "1(Yes)" to use DHW function.
Heat Pump Variables for Controlling DHW Tank
• Maximum DHW tank temperature with R410A(refrigerant) heat pump operation :
FSV #3021, Default 50˚C, Range : 45 ~ 55˚C.
• Temperature difference determining the heat pump OFF temperature :
FSV #3022, Default 2˚C, Range : 2 ~ 10˚C.
• Temperature difference determining the heat pump ON temperature :
FSV #3023, Default 5˚C, Range : 1 ~ 20˚C.
• DHW heating mode timer : I f there is simultaneous requests of space heating/cooling and
- F SV #3024(minimum DHW operating time, Default 5 min., Range 0 ~ 20 min.),
#3025(maximum DHW time, Default 30 min., Range 5 ~ 95 min.), #3026(time interval
between two consecutive DHW mode operations, Default 3 hour, Range 0 ~ 10 hour)
The FSV #4011 for DHW priority should be set to "0(DHW)"(Default) for the mode timer
action as mentioned above.
If not, the space heating mode by heat pump has a priority over the DHW heating mode
under the specified low outdoor temperature(#4012).
RC120MHXGA_IB_E_34412A(1).indd 37
Field Setting Value
Description
Sub Code Default
Application
11
Max Temp
21
Stop
22
Start
23
Min Operation
24
Max Operation
25
Interval
26
Application
31
Delay Time
32
Overshoot
33
Compensation Temp
34
Application
41
Interval
42
Start Time
43
Target Temp
44
Duration
45
Timer OFF Function
51
Timer Duration
52
H/P Combination
61
DHW valve or 3-way
71
valve
Zone #1
72
Zone #2
73
DHW heating, this mode timer will toggle operation modes.
Min
Max
Step
0(No)
0
1(Yes)
50
45
55
2
2
10
5
1
20
5
1
20
30
5
95
3
0.5
10
0.5
1(On)
0(Off)
1
20
20
95
0
0
4
10
0
20
1(On)
0(Off)
1
Fri
Mon
Sun
1(All)
23
0
23
70
40
70
10
5
60
0(Off)
0
1
60
30
300
10
1(Yes)
0(No)
1(Yes)
0(Tank)
0
1(Room)
1(Room)
0
1
1(Room)
0
1
Operating advanced function _37
Unit
-
-
1
˚C
1
˚C
1
˚C
1
min
5
min
hour
-
-
5
min
1
˚C
1
˚C
-
-
day
1
o'clock
5
˚C
5
min
-
-
min
-
-
-
-
-
-
-
-
2012-02-08 오후 2:35:51