3

Functions

Notes
● Refer to the WEB Browser Operation Manual for operating the GB-24A.
● Use the initial setting web to make initial settings via LAN.

3-1. Specifications

Item
Interface
Environmental condition
Dimensions
Weight
Installation Environment
Number of control units
Table 3-1. Specifications
M-NET:
30V DC/24V DC;0.13/0.15A
LAN:
Ethernet 10Base-T
Input/output: 12V DC or 24V DC, (External power supply)
Temperature
Operating range: 32 to 104ºF / 0 to 40ºC
Storage range:
Humidity
30~90%RH (No condensation)
1
7
5
/
(H) ✕ 9
/
(W) ✕ 1
8
8
1
2
/
lb/1.1kg
2
In control panel box (indoor)
Install this product indoors.
*This unit is installed and used in a business office, homes or equivalent
environment.
Indoor units, independent OA processing units or LOSSNAY
: 24 units maximum (24 groups maximum)
Number of units (indoor, independent OA processing, or LOSSNAY) in one
group
: 1-16 units
*Note: Indoor units, independent OA processing units, and LOSSNAY
can not register to the same group.
Number of remote controllers in one group
: 1-2
Number of system controllers in one group
: 0-4 (including the number of remote controller in one group)
: 0-3 for groups which have one remote controller.
Number of indoor units interlocked with one OA processing unit or
LOSSNAY
: 0-16 (some types of OA processing unit can only be operated
when interlocked to a maximum of 9 units)