Address
4707H
Lower-limit of temperature range
4708H
PB Proportional band
4709H
Ti Integral time
470AH
Td Derivative time
470BH
Heating/Cooling hysteresis
470CH
Regulate 20mA current output deviation
470DH
Regulate 4mA current output deviation
470EH
Default value of integral volume
4710H
Input temperature sensor type
4711H
Control method
4712H
Heating/Cooling control cycle
4713H
Proportional control offset error value
4714H
Temperature regulation value
4715H
Alarm 1 type
4716H
Alarm 2 type
4717H
Temperature unit display selection
4718H
Heating/Cooling control Selection
4719H
Control Run/Stop setting
471AH
Communication write-in selection
471BH
Software version
471CH
Read LED status
471DH
Read KEY status
471EH
Read output amount
4729H
AT Setting
472AH
Write output amount
Code 0
Code 1
Code 2
Code 3
472BH (R)
Code 4
Code 5
Code 6
Code 7
4731H
Read / Write lock status
4732H
Event input switch
4733H
CT monitor value
Note: R refers to "read only" value
Default Communication Response Setting
Write hex value 1234 into register at 471BH and 1234 again into register at 4724H. Re-power DTA to complete the default setting.
Content
The data content should not be lower than the temperature range
0.1 ~ 999.9, Unit: 0.1
0 ~ 9,999
0 ~ 9,999
0 ~ 9,999
-100 ~ 54 (1 unit = 0.1mA)
-39 ~ 100 (1 unit = 0.1mA)
0 ~ 100%
Please refer to the contents of the "Temperature Sensor Type and Temperature
Range" for detail
0: PID (default), 1: ON/OFF,
2: manual tuning
1 ~ 99 second
0% ~100%
-999 ~ 999, Unit: 0.1
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
o
C : 1 (default),
Heating: 0 (default), Cooling: 1
Run: 1 (default), Stop: 0
Communication write in disabled: 0 (default), Communication write in enabled: 1
V1.00 indicates 0 x 100
b2: °F, b3: °C, b4: AL2, b5: AL1, b6: OUT, b7: AT
b0: SET, b1: Select, b2: Up, b3: Down
Unit: %
OFF: 0 (default), ON:1
Available on "manual control" only
Normal operation (No error)
Initial process
Initial status (Temperature is not stable)
Temperature sensor is not connected
Temperature sensor input error
Measured temperature value exceeds the temperature range
No Int. error
EEPROM Error
0: No Lock, 1: Lock1, 11: Lock2, 21: Lock3
0: Event disable, 1: SV switch, 2: Run/Stop
Unit is 0.1A
Explanation
o
F : 0
- 8 -