Advertisement
Electric Shock!
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a serious human injury or serious property damage may occur.
1 | Series | DTA: Delta A Series Temperature Controller |
2 | Panel Size | 4848, 4896, 9648, 7272, 9696 |
3 | Output Selection | R: Relay output, SPDT (SPST: 1/16 DIN size), 250VAC, 5A V: Voltage Pulse output, 14V+10% ~ -20% (Max. 40mA) C: Current output, 4~20mA |
4 | Communication (Optional) | 0: No interface 1: RS-485 |
5 | Current Transformer (Optional) | None: No CT function (Current transformer is not provided) T: Current transformer is provided (only DTA7272 series support) |
Input voltage | 100 ~ 240VAC, 50/60Hz |
Display method | 7-segment digit LED Display Process value (PV): Red, Set point (SV): Green |
Sensor type | Thermocouple: K, J, T, E, N, R, S, B, U, L, Txk |
3-wire Platinum RTD: Pt100, JPt100 Copper resistor: Cu50 | |
Control mode | PID, ON/OFF control or Manual tuning |
Display accuracy | 0.1% of measuring range |
Sampling rate | 500 msec/per scan |
Ambient temperature | 0o C ~ 50o C |
Relative humidity | 35% ~ 80% (non-condensing) |
LED Display | Explanation | Default |
RUN/STOP: Control setting begins. Run ( ) or Stop ( ) mode on the SV display. | RUN | |
ALARM1 HIGH: Upper-limit alarm 1 | 4.0 oC | |
ALARM1 LOW: Lower-limit alarm 1 | 4.0 oC | |
ALARM2 HIGH: Upper-limit alarm 2 | 4.0 oC | |
ALARM2 LOW: Lower-limit alarm 2 | 4.0 oC | |
Setting lock: Lock 1 ( ), Lock 2 ( ) or OFF ( ) on the SV display. Lock 1 mode can lock all settings and Lock 2 mode only can lock others than SV value. When OFF mode is selected, the Lock function will be OFF. If you press and key simultaneously, the "Lock" status can be released and the controller will be back to the previous display. | OFF | |
OUT: Output value display and output value adjustment in manual tuning control | 0 | |
CT: In case of using an external current transformer (CT), the controller displays the current value being measured by CT, if the control output is ON | Read only |
LED Display | Explanation | Default |
AT: Auto-tuning setting. When AT key is set to ON ( ). | OFF | |
P: Proportional Band (PID control) | 47.6 | |
I: Integral Time (PID control) | 260 | |
D: Derivative Time (PID control) | 41 | |
PdoF: Offset output when P or PD control function is ON. | 0 | |
ioF: Default value of integral volume when PID control function is ON and integral time constant is not equal to 0(zero). | 0 | |
HTS: Set Heating hysteresis when ON/OFF control function is ON. | 0 | |
CTS: Set Cooling hysteresis when ON/OFF control function is ON. | 0 | |
HTPD: PID heating control cycle setting (PID control) | C, V: 4sec | |
CLPD: PID cooling control cycle setting (PID control) | R: 20sec | |
TPOF: Regulate temperature deviation value | 0 | |
TPGN: Regulate temperature gain value | 0 | |
CRHI: Regulate 20mA output deviation value | 0 | |
CRLO: Regulate 4mA output deviation value | 0 |
LED Display | Explanation | Default |
INPUT: Select input temperature sensor type | PT2 | |
UNIT: Temperature display unit, C ( ) and F ( ) | oC | |
T-HIGH: Upper limit for temperature range | 500.0 | |
T-LOW: Lower limit for temperature range | -20.0 | |
CONTROL: Control method setting on the SV display: PID ( ), ON/OFF control ( ), or manual tuning ( ) | PID | |
SWITCH: Select Heating ( ) or Cooling ( ) action | HEAT | |
AL1 SET: Alarm 1 setting | 0 | |
AL2 SET: Alarm 2 setting | 0 | |
C SELECT : ASCII, RTU communication formats selection | ASCII | |
C WE: Write-in function disable/enable | OFF | |
C NO: Address setting | 1 | |
BPS: Baud rate setting | 9,600 | |
LENGTH: Data length setting | 7 | |
PARITY: Parity bit setting | E | |
STOP BIT: Stop bit setting | 1 |
Sensor type | Display | Range | Sensor type | Display | Range |
Pt100 | 0.0 ~ 100.0°C | E | 0 ~ 600°C | ||
Pt100 | -20.0 ~ 500.0°C | T | -20.0 ~ 400.0°C | ||
Pt100 | -200 ~ 600°C | T | -200 ~ 400°C | ||
JPt100 | 0.0 ~ 100.0°C | J | -20.0 ~ 400.0°C | ||
JPt100 | -20.0 ~ 400.0°C | J | -100 ~ 850°C | ||
Cu50 | -50.0 ~ 150.0°C | K | -20.0 ~ 500.0°C | ||
Cu50 | -50 ~ 150°C | K | -200 ~ 1300°C | ||
B | 100 ~ 1800°C | L | -200 ~ 850°C | ||
S | 0 ~ 1,700°C | U | -200 ~ 500°C | ||
R | 0 ~ 1,700°C | Txk | -200 ~ 800°C | ||
N | -200 ~ 1,300°C |
Set Value | Alarm Type |
0 | Alarm function disabled |
1 | Deviation upper- and lower-limit: This alarm output operates when PV value is higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L). |
2 | Deviation upper-limit: This alarm output operates when PV value is higher than the setting value SV+(AL-H). |
3 | Deviation lower-limit: This alarm output operates when PV value is lower than the setting value SV-(AL-L). |
4 | Reverse deviation upper- and lower-limit: This alarm output operates when PV value is in the range of the setting value SV+(AL-H) and SV-(AL-L). |
5 | Absolute value upper- and lower-limit: This alarm output operates when PV value is higher than the setting value AL-H or lower than setting value AL-L. |
6 | Absolute value upper-limit: This alarm output operates when PV value is higher than the setting value AL-H. |
7 | Absolute value lower-limit: This alarm output operates when PV value is lower than the setting value AL-L. |
8 | Deviation upper- and lower-limit with standby sequence: This alarm output operates when PV value reaches set value (SV value) and the value is higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L). |
9 | Deviation upper-limit with standby sequence: This alarm output operates when PV value reaches set value (SV value) and the reached value is higher than the setting value SV+(AL-H). |
10 | Deviation lower-limit with standby sequence: This alarm output operates when PV value reaches the set value (SV value) and the reached value is lower than the setting value SV-(AL-L). |
11 | Hysteresis upper limit alarm output: this alarm output operates if PV value is higher than the setting value SV+(AL-H). This alarm output is OFF when PV value is lower than the setting value SV+(AL-L). |
12 | Hysteresis lower limit alarm output: this alarm output operates if PV value is lower than the setting value SV-(AL-H). This alarm output is OFF when PV value is higher than the setting value SV-(AL-L). |
13 | CT alarm output: This alarm operates when the current measured by transformer (CT) is lower than AL-L or higher than AL-H (This alarm output is available only for the controller with current transformer). You can set current alarm range between 0.5A ~ 30A, display resolution is 0.1A and measure accuracy is +/- 0.5A. |
Address | Content | Explanation |
4700H (R) | Process value (PV) | Measuring unit is 0.1 oC or oF |
4701H | Set point (SV) | Unit is 0.1, oC or oF |
4702H | Upper-limit alarm 1 | |
4703H | Lower-limit alarm 1 | |
4704H | Upper-limit alarm 2 | |
4705H | Lower-limit alarm 2 | |
4706H | Upper-limit of temperature range | The data content should not be higher than the temperature range. |
4707H | Lower-limit of temperature range | The data content should not be lower than the temperature range. |
4708H | PB Proportional band | 0.1 ~ 999.9, unit is 0.1 |
4709H | Ti Integral time | 0 ~ 9,999 |
470AH | Td Derivative time | 0 ~ 9,999 |
4711H | Control method | 0: PID, 1: ON/OFF, 2: manual tuning |
4714H | Temperature regulation value | -999 ~ 999, unit: 0.1 |
4718H | Heating/Cooling control Selection | Heating: 0 (default), Cooling: 1 |
4719H | Control Run/Stop setting | Run: 1 (default), Stop: 0 |
4729H | AT setting | Off: 0 (default), On: 1 |
4733H | CT monitor value | Unit is 0.1A |
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Delta A Series (DTA) - Temperature Controller Instructions
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the A Series that isn't answered in the manual? Leave your question here.