Series Temperature Controller Instruction Sheet
 Precaution
DANGER! Caution! Electric Shock! Do not touch the AC terminals while the power is supplied to the controller to prevent electric
shock. Make sure power is disconnected while checking the unit inside.
This controller is an open-type temperature controller. Be sure to evaluate any dangerous application in which a serious human
injury or serious property damage may occur.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.2 mm). Make sure all wires are
connected to the correct polarity of terminals.
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning. Never modify or disassemble the
controller. Do not connect anything to the "No used" terminals.
3. To prevent interference, keep away from high voltage and high frequency when installing. Do not install and/or use the controller in
places subject to:
(a) Dust or corrosive gases and liquid; (b) High humidity and high radiation; (c) Vibration and shock;
4. Power must be off when wiring and replacing a temperature sensor.
5. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
6. Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD).
7. Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please route
power wires as far as possible from load wires to prevent interference and induced noise.
8. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water,
corrosive materials, airborne dust, and electric shock or vibration.
9. Make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious
damage may occur.
10. Do not touch the terminals in the controller or try to repair the controller when power is on, in order to prevent electric shock.
11. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit
within this period.
12. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
 Display, LED & Pushbuttons
PV: Present value
SV: Set value
,
: Celsius or Fahrenheit LED
1, 2: ALM1/ALM2 alarm output LED
A/M: Auto-Tuning and manual mode LED
OUT1, OUT2: Output LED
: "Select" and "Set up" keys
: "Set value tuning" keys
2015/4/8
1

Advertisement

Table of Contents
loading

Summary of Contents for Delta DTK Series

  • Page 1 2015/4/8 Series Temperature Controller Instruction Sheet  Precaution DANGER! Caution! Electric Shock! Do not touch the AC terminals while the power is supplied to the controller to prevent electric shock. Make sure power is disconnected while checking the unit inside. This controller is an open-type temperature controller.
  • Page 2: Ordering Information

     Ordering Information DTK 1 2 3 4 5 6 7 Series DTK: Delta DTK Series Temperature Controller 4848:4848 1/16 DIN W48 × H48mm 7272:7272 W72 × H72mm Panel Size (W×H) 4896:4896 1/8 DIN W48 × H96mm 9696:9696 1/4 DIN W96 × H96mm...
  • Page 3 Parameter Settings for Operation Mode: Factory Display Description Setting to set temperature set point. Press to switch between display parameters. RUN/STOP: Control setting RUN/STOP SELECT POINT: Decimal point setting (0: integral; 1: one decimal point) LOCK: Setting lock mode (LOCK1: all; LOCK2: only SV is allowed) ALARM1 HIGH: Upper limit alarm 1 (display according to the setting in ALARM mode) ALARM1 LOW: Lower limit alarm 1 (display according to the setting in ALARM mode) ALARM2 HIGH: Upper limit alarm 2 (display according to the setting in ALARM mode)
  • Page 4: Display Unit Setting

    Parameter Settings for Regulation Mode: Factory Display Description Setting  AT: Auto-tuning Switch (display when setting Ctrl = PID/RUN) Press P: Proportional Setting (display when setting Ctrl = PID and TUNE = AT) 47.6 I: Integral Time Setting (display when Crtl = PID; this parameter is set automatically when TUNE = AT.) D: Deviation Time Setting (display when Crtl = PID;...
  • Page 5  Set Value and Upper/Lower Limit of the Input Value SV setting serves as reference for control.  Set the Upper Limit of Input Value: In Initial Setting Mode parameter , the upper limit input value must be set within the range shown in the chart "Temperature Sensor Type &...
  • Page 6: Control Mode Setting

     Selection for Heating/Cooling/Alarm/Dual-Loop Output Control DTK series features 1 set of Output Control (OUT1) and 1 set of Alarm Output (ALARM1), both of which are built-in. Users can also purchase a 2nd set of Alarm Output (ALARM2).  Using 1 set of Output Control: In Initial Setting Mode, set parameter to Heating (H1) or Cooling (C1) mode.
  • Page 7: Tune Function

    (output 2).  Setting of Dead Band for both outputs: Set Dead Band via parameter in Regulation Mode.  PID Mode: When setting for heating or cooling, the program performs PID operation via input temperature and setting temperature, with the operation result output for control of the temperature. A PID parameter and control period must be set for this function; these parameters can also be generated automatically via auto-tuning (AT).
  • Page 8: Restore Factory Settings

     When setting the SV value, range for the setting will be limited to 0 ~ 200 .  Under ON-OFF and PID control conditions, the control output will be forced to shut off if the PV value exceeds the upper/lower limit. (Alarm output is still normal) ...
  • Page 9 Hysteresis upper limit alarm output: This alarm output operates when PV value is higher than the setting value SV+(AL-H). This alarm output is OFF when PV value is lower than the setting value SV+(AL-L). SV+(AL-L) SV+(AL-H) Hysteresis lower limit alarm output: This alarm output operates when PV value is lower than the setting value SV-(AL-H).
  • Page 10 The setting of Dead Band when Dual Loop 100FH -999 ~ 9999 output controls are used. 1010H Hysteresis setting of the 1st output group 0~9999 1011H Hysteresis setting of the 2nd output group 0~9999 1012H Read Output 1 amount Unit is 0.1%. 1013H Read Output 2 amount Unit is 0.1%.
  • Page 11: Panel Cutout

    data (word/bit) 1000H/081xH CRC 1 CRC 1 CRC 1 Address data 1001H CRC 0 CRC 0 CRC 0 CRC 1 CRC 0 CRC check code: CRC (Cyclical Redundancy Check) is obtained via the following steps. 1. Load in a 16-bit register FFFFH as the CRC register. 2.

Table of Contents