Set value
Reverse deviation upper- and lower-limit:
4
This alarm output operates when PV value is in the range of the setting value SV + (AL-H) and
SV - (AL-L).
Absolute value upper- and lower-limit:
5
This alarm output operates when PV value is higher than the setting value AL-H or lower than
setting value AL-L.
Absolute value upper-limit:
6
This alarm output operates when PV value is higher than the setting value AL-H.
Absolute value lower-limit:
7
This alarm output operates when PV value is lower than the setting value AL-L.
Deviation upper- and lower-limit with standby sequence:
8
This alarm output operates when PV value reaches set value (SV value) and the value is
higher than the setting value SV + (AL-H) or lower than the setting value SV - (AL-L).
Deviation upper-limit with standby sequence:
9
This alarm output operates when PV value reaches set value (SV value) and the reached
value is higher than the setting value SV + (AL-H).
Deviation lower-limit with standby sequence:
10
This alarm output operates when PV value reaches the set value (SV value) and the reached
value is lower than the setting value SV - (AL-L).
Hysteresis upper limit alarm output: this alarm output operates if PV value is higher than the
11
setting value SV + (AL-H). This alarm output is OFF when PV value is lower than the setting
value SV + (AL-L).
Hysteresis lower limit alarm output: this alarm output operates if PV value is lower than the
12
setting value SV - (AL-H). This alarm output is OFF when PV value is higher than the setting
value SV - (AL-L).
CT alarm output:
This alarm operates when the current measured by transformer (CT) is lower than AL-L or
13
higher than AL-H (This alarm output is available only for the controller with current
transformer).
Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L.
With standby sequence: Meaning that the alarm output would be temporarily disabled until the PV value reaches the set value. Then, the
alarm output will operate.
Current Transformer (CT) Function
The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with the controller, change the
corresponding alarm output mode to mode 13 (alarm output set value is 13), then turn to operation mode and set the current lower-limit and
current upper-limit. You can set current alarm range between 0.5A ~ 30A, display resolution is 0.1A and measure accuracy is +/- 0.5A.
Communication Parameters List
Controller offers a RS-485 port for serial communication.
Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps
Communication protocol: Modbus (ASCII)
Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2
Available communication address: 1 to 255, 0 is broadcast address
Function code: 03H to read the contents of register (Max. 3 words); 06H to write 1 (one) word into register.
Address
4700H (R)
Process value (PV)
4701H
Set point (SV)
4702H
Upper-limit alarm 1
4703H
Lower-limit alarm 1
4704H
Upper-limit alarm 2
4705H
Lower-limit alarm 2
4706H
Upper-limit of temperature range
Alarm type
Content
Measuring unit is 0.1, updated one time in 0.5 second
Unit: 0.1 (
The data content should not be higher than the temperature range
Explanation
o
o
C or
F)
- 7 -
Alarm output operation
ON
OFF
SV-(AL-L)
SV
SV+(AL-H)
ON
OFF
AL-H
AL-L
ON
OFF
AL-H
ON
OFF
AL-L
ON
OFF
SV-(AL-L)
SV+(AL-H)
SV
ON
OFF
SV
SV+(AL-H)
ON
OFF
SV-(AL-L)
SV
ON
OFF
SV
AL-L
AL-H
ON
OFF
AL-H AL-L SV
ON
OFF
AL-L
SV
AL-H