Advanced Settings--
Special access
required. Contact
Wine Guardian
Service Department
for access code
Compressor anti-
short cycling time
Set up remote sensor
or remote interface
controller
Room sensor
calibration
Setting 8
 Press "Mode" button to advance to Setting 8.
 Press the up or down arrow buttons to adjust
number to the access code. Press "Mode"
button to continue onto setting 9 through 19.
Setting 9
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER THAN
FACTORY DEFAULT.
 Press "Mode" button to advance to Setting 9.
 Press the "Up" or "Down" arrow buttons to
adjust to the desired time in one (1) minute
increments. Maximum is 10 minutes,
minimum is 0 minutes.
Compressor anti-short cycling time is the
amount of allowable time between compressor
stop and restart. Rapid start/stop of compressors
can cause premature failure. Factory default is 5
minutes.
Setting 10
 Press "Mode" button to advance to Setting 10.
 Press the "Up" or "Down" arrow buttons to
adjust to the desired setting.
rS = Remote sensor
rI = Remote interface
LI= Local interface – Through-the-wall unit
only
A = Averaging – Jumper position within
sensors must be adjusted. See page 44.
Setting 15
 Press "Mode" button to advance to Setting 15.
 Press the "Up" or "Down" buttons to adjust to
the desired set point. Maximum setting is +5,
minimum setting is -5. Factory default is zero
(0). Sensor calibration set point changes the
actual display reading (temperature only) by
the value of this setting.
Example: Sensor reading = 55 Deg F
Setting 15 set to +4
Display reading = 59 Deg F