7-2. Check Method
On the remote controller (Main remote controller, Central control remote controller) and the interface P .C. board
of the outdoor unit, a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P .C.
board) to display the operation is provided. Therefore the operation status can be known. Using this self-diagno-
sis function, a trouble or position with trouble of the air conditioner can be found as shown in the table below.
7-2-1. Check Code List
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See "Main remote controller display" in the list.
• In case of check from outdoor unit: See "Outdoor 7-segment display" in the list.
• In case of check from AI-NET central control remote controller: See "AI-NET central control display" in the list.
• However connection with AI-NET central control is disabled for the wall type (2 series).
• In case of check from indoor unit with wireless remote controller: See "Sensor block display of receiving unit"
in the list.
Check code
Outdoor 7-segment display
Main remote
controller
display
Sub code
E01
—
E02
—
—
E03
E04
—
No. of indoor units in which sensor
E06
E06
has been normally received
E07
—
E08
E08 Duplicated indoor addresses
E09
—
01: Indoor/Outdoor communication
E12
E12 02: Communication between
outdoor units
E15
E15
00: Capacity over
E16
E16
01: No. of connected units
E18
—
00: No header unit
E19
E19
02: Two or more header units
01: Outdoor of other line connected
E20
E20
02: Indoor of other line connected
E23
E23
E25
E25
No. of outdoor units which
E26
E26
received signal normally
E28
E28 Detected outdoor unit number
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
E31
E31 04: Fan IPDU error
05: IPDU + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
IPDU: Intelligent Power Drive Unit
¡ : Lighting,
ALT.: Flashing is alternately when there are two flashing LED.
SIM: Simultaneous flashing when there are two flashing LED
AI-NET central
control display
—
—
—
—
—
97
—
04
04
—
—
96
—
99
42
—
42
89
—
97, 99
96
42
—
15
—
15
15
d2
CF
¤
: Flashing,
Wireless remote controller
Sensor block display
of receiving unit
Ready Timer
Flash
Operation
Communication error between indoor and
l
l
¤
remote controller
(Detected at remote controller side)
l
l
¤
Sending error of remote controller
l
l
Communication error between indoor and
¤
remote controller (Detected at indoor side)
l
l
Communication circuit error between indoor
¤
and outdoor (Detected at indoor side)
l
l
¤
Decrease of No. of indoor units
l
l
Communication circuit error of indoor and
¤
outdoor (Detected at outdoor side)
l
l
¤
Duplicated indoor addresses
l
l
¤
Duplicated master remote controllers
l
l
¤
Automatic address start error
l
l
¤
No indoor automatic address
l
l
¤
No. of connected indoor units / Capacity over
l
l
Communication error between indoor header
¤
and follower units
l
l
¤
Outdoor header units quantity error
l
l
Other line connected during automatic
¤
address
l
l
Sending error in communication between
¤
outdoor units
l
l
¤
Duplicated follower outdoor addresses
l
l
¤
Decrease of No. of connected outdoor units
l
l
¤
Follower outdoor error
l
l
¤
IPDU communication error
38
FILE NO. SVM-05052
l
: Goes off
Check code name
Judging
device
Remote
controller
Remote
controller
Indoor
Indoor
I/F
I/F
Indoor /
I/F
Remote
controller
I/F
I/F
I/F
Indoor
I/F
I/F
I/F
I/F
I/F
I/F
I/F