EXCEL 50 INSTALLATION INSTRUCTIONS
containing a C-Bus connection in order to support
use of the XI584 User Interface.

B-Port

Select 'B-Port" and confirm with ENTER. The following screen
appears:
B-Port Config.
Baudrate:
Move the cursor with the arrow keys to the field to set baud
rate for the B-Port. Use the '+' and '–' keys to edit the fields.
Confirm with ENTER.
NOTE: Live CARE is now capable of autodetecting the con-
troller baud rate setting, then switching it temporarily
to 38.4 Kbaud. When Live CARE is disconnected,
the controller will switch back to the previous baud
rate setting automatically within 15 seconds.
Move the cursor to the 'BACK' field with the arrow keys.
Confirm with ENTER.

C-Bus

Select 'C-Bus" and confirm with ENTER. The following screen
appears:
C-Bus Config.
Baudrate:
Contr.No:
NOTE: If you set the bus ID to a non-zero value, the C-bus
baudrate will be immediately disabled (i.e. it is then
no longer editable). See also section "
LON-Bus (i.e. LonWorks Network)" below.
If 'Baudrate' is selected:
Move the cursor with the arrow keys to the field to set baud
rate for the C-Bus. Use the '+' and '–' keys to edit the fields.
Confirm with ENTER.
If 'Contr. No.' is selected:
Set the controller number using the '+' or '–' keys. Confirm
with ENTER.
IMPORTANT
If no controller number is set or if the number shown
is not reconfirmed, the controller will not go online on
the C-Bus after start-up.
Move the cursor to the 'BACK' field with the arrow keys.
Confirm with ENTER.

LON-Bus (i.e. LonWorks Network)

Select 'LON-Bus" and confirm with ENTER. The following
screen appears:
EN1B-0101GE51 R1105D
9600
BACK
76800
BACK
LON-Bus Config.
Contr. Neuron ID
<
neuron ID number
Bus ID
IMPORTANT
The bus ID is a non-unique number (i.e. different
Excel 500 controllers can have the same bus ID in
common) between 0 and 99 (inclusive) which the
user can edit after a reset during the controller's
start-up sequence or by changing the configuration
property nciXL500BusSetup. The factory default is
"0", which enables C-Bus and Standard L
communication. Assigning a bus ID other than "0" will
enable L
W
ON
ORKS
Management functionality and disable C-Bus
communication.
This screen displays the unique identification number for the
Neuron chip in the controller.
Move the cursor to the 'BACK' field with the arrow keys.
Confirm with ENTER.

Meter-Bus

Select 'M-Bus" and confirm with ENTER. The following screen
appears:
M-Bus Config.
Baudrate:
BACK
Move the cursor with the arrow keys to the field to set baud
rate for the Meter Bus. Use the '+' and '–' keys to edit the
fields. Confirm with ENTER.
Move the cursor to the 'BACK' field with the arrow keys.
Confirm with ENTER.

Modem Communication

Select 'Modem' and confirm with ENTER. The following
screen appears:
Enable/Disable
Modem Part:
<
ENABLE/DISABLE
This screen allows the user to enable modem communication.
If modem communication is enabled, 'DISABLE' will appear,
while 'ENABLE' will appear if it is currently disabled. To
change the current setting, move the cursor to the
enable/disable field, and select it by pressing ENTER.
Change the setting with the '+' or '-' keys. Confirm with
ENTER.
34
>
BACK
ON
communication with Building
9600
>
NEXT
W
ORKS