Connection Examples
Fig. 29. Digital outputs, connection of relay
Fig. 30. Digital outputs, direct connection of 3-position
actuators
Power Supply
The Excel 50 Controller is powered by an external trans-
former.
Transformer requirements for one Excel 50 Controller:
24 Vac ±20%
Voltage
Current
3 A, if fully equipped (6 DO's x 0.4 A)
2 A, if current of DO's does not exceed 1.8 A
Power
72 VA, if fully equipped
The transformer, already installed in the cabinet, can be used
to supply several controllers, communication devices or peri-
pherals (actuators, etc.) if the transformer provides sufficient
power.
Fig. 31. Transformer example
EXCEL 50 INSTALLATION INSTRUCTIONS
CRT-Series
Table 12. No. of controllers connected to one transformer
transformer
CRT 2
CRT 6
CRT 12
Use quick-acting backup fuse 10 A (or automatic H16 or L16)
to protect the transformer primary side. On the primary side of
the CRT 2, there is a fusible output of type M 0.315 A (T)
250 V for the purpose of fine fusing.
Table 13. Overview of CRT Series AC/DC current
transformer
max. AC current
CRT 2
CRT 6
CRT 12
Fig. 32. AC/DC current graphs
1450 Series
Table 14. 1450 Series transformers
part #
primary side
1450 7287
-001
120 Vac
-002
120 Vac
-003
120 Vac
-004
240/220 Vac
-005
240/220 Vac
-006
240/220 Vac
All transformers of the 1450 series are designed for 50/60 Hz
AC and have insulated accessory outputs. The transformers
include built-in fuses, line transient/surge protection and AC
convenience outlets and meet NEC class 2 requirements.
17
Excel 50 controller
1 (1.8 A max.)
2
4
max. DC current
2 A
0.5 A = 500 mA
6 A
1.3 A = 1300 mA
12 A
2.5 A = 2500 mA
secondary side
24 Vac, 50 VA
2 x 24 Vac, 40 VA and 100 VA
from separate transformer
24 Vac, 100 VA and 24 Vdc
600 mA
24 Vac, 50 VA
2 x 24 Vac, 40 VA and 100 VA
from separate transformer
24 Vac, 100 VA and 24 Vdc,
600 mA
EN1B-0101GE51 R1105D