EXCEL 50 INSTALLATION INSTRUCTIONS
CONFIG
C1 -1
C2 -1
C3 -1
C4 -1
C5 -1
C6 -1
The codes of the configurable application can be changed In
this screen. The application codes can be generated with the
'LIZARD-Excel 50 Application Selector'. This screen does not
appear with standard and custom CARE applications.
NOTE: Not all applications have six configuration code
numbers. Applications with eight configuration codes
have two on a second screen as shown below.
First screen:
C1 -1
C3 -1
C5 -1
Second screen:
CONFIG
C7 -1
NOTE If the 'LIZARD-Excel 50 Application Selector' is not
available, please contact your local Honeywell branch
for support.
Select the appropriate code and change its value using the '+'
and '–' keys.
Move the cursor to the 'CONFIG' field. Confirm with ENTER.
If the codes entered in the screen are allowed, the default
screen of normal operation will show up:
1. time program
<
MON 13.06. 10:27
TO: 20:30
TODAY
If one or more codes entered are not allowed, the initialization
screen will show up again. Change the screens by selecting
NEXT and confirming with ENTER until you have reached the
configuration screen again. Codes which are not allowed have
the value '-1' instead of the previously entered code. Change
the codes until all codes are correct.
You will now come to the default screen of normal operation:
1. time program
<
MON 13.06. 10:27
TO: 20:30
TODAY
EN1B-0101GE51 R1105D
C2 -1
C4 -1
C6 -1
NEXT
C8 -1
>Init
20°C
NEXT
>Init
20°C
NEXT

Request Download

Contr. Setup
Select Applic.
Requ. Download
DP Wiring Check
If 'Requ. Download' has been selected from the screen shown
above, the following screen appears.
Please execute
Download
Follow the instructions for a download given in the XI584 User
Guide or Lizard User Guide (if downloading via B-Port) or the
User Guide for the Building Central (if by C-Bus).
NOTE: After download of an application, the controller
checks the user ID via its checksum and will not start
the application if it is invalid. An alarm "Invalid User
ID" will be issued.

Datapoint Wiring Check

Contr. Setup
Select Applic.
Requ. Download
DP Wiring Check
If 'DP Wiring Check' has been selected from the screen
shown above, default user addresses are generated following
the following pattern:
• AI0101: Analog input, board 1, input 1
• AO0201: Analog output, board 2, output 1
• DI0301: Digital input, board 3, input 1
• DO0401: Digital output, board 4, output 1
NOTE: The board numbers shown above are internal
references and are not relevant to the user. In Excel
50 Controllers the numbers are fixed for the I/O type,
i.e. analog inputs are always AI01, digital inputs are
always DI03, etc.
After generating the default addresses, the following screen
appears:
Default Points
Alarm History
Select
— 'Default Points' to display I/O points for checking values
and manually setting outputs for testing.
— 'Alarm History' to display current alarms. This feature
allows the system to be checked out by a single person
opening and closing inputs and then later reading the
36