Table 6-1: Annunciator Point Functions - Fire-Lite AFM-16ATX User Manual

Annunciator modules for fire-lite fire alarm control panels
Table of Contents

Advertisement

Annunciator Operation
Annunciator points "track" or follow those system points they are programmed to
annunciate; they do not latch. Table 6-1 outlines the annunciation of various System
circuits and functions. Note: Control Switches marked "not used" will still function as local
LAMP TEST or local ACKNOWLEDGE switches for their respective points.

Table 6-1: Annunciator Point Functions

Circuit Type
IZ-8F circuit
M
O
IC-4F/ICE-4F circuit
D
U
CR-4F/CRE-4F circuit
L
E
S
TC-2F, TC-4F
VC-4F, DC-4F circuit
ANNUNCIATOR
POINT # 1
ANNUNCIATOR
POINT # 2
ANNUNCIATOR
POINT # 3
C
P
ANNUNCIATOR
U
POINT # 4
ANNUNCIATOR
2
POINT # 5
0
ANNUNCIATOR
0
POINT # 6
0
ANNUNCIATOR
POINT # 7
ANNUNCIATOR
POINT # 8
1 If the Eight-Point Shift (DIP switch # 4) is set "ON", the eight CPU functions will be shifted from
annunciator points 1 thru 8 to points 57 thru 64 (provided those points exist in the system).
2 These control switches are active only if all of these conditions are set:
a) Receive Only (DIP Switch # 5) is set to "OFF."
3 If an IZ-8F or IZ-4F circuit is programmed on the system as a supervisory point, both the red and
yellow LEDs will be illuminated for a supervisory condition. Illumination of the yellow LED alone
indicates a trouble condition (open circuit) on the IZ-8F supervisory circuit.
4 If a UDACT-F is employed on a system with an annunciator, point assignments for the first eight
yellow LEDs on the annunciator will change. Refer to the UDACT-F Manual and the appropriate
FACP Manual.
AFM-16ATX & AEM-16ATF
AFM-32AX
& AEM-32AF
Red LED
Indicates alarm
status of circuit
Indicates Activation
Indicates Activation
Indicates Activation
1
Indicates
System Alarm
not used
not used
not used
Indicates that Notification
Circuit 1 has been activated
Indicates that Notification
Circuit 2 has been activated
Indicates that the Remote
Signalling Municipal Tie
has been activated
Indicates that
the Alarm Relay
has been
activated
b) Switch Inhibit (DIP Switch # 7) is set to "OFF."
15390 Rev D 8/2/96 P/N 15390:D
Yellow LED
3
Indicates trouble
status of circuit
Indicates trouble
status of circuit
Indicates trouble
status of relay
Indicates trouble
status of relay
Indicates
System Trouble
Indicates that signals
have been silenced
not used
Indicates
Supervisory condition
Indicates trouble
status of circuit
Indicates trouble
status of circuit
Indicates trouble
status of circuit
Indicates
Module Trouble,
Power Failure or
Disabled Circuit(s)
2
Control Switch
not used
Control
Notification Circuit
Controls
Relays
Remote Switch
Functions
Functions as an
ACKNOWLEDGE
Functions as a
SIGNAL SILENCE
Functions as a
SYSTEM RESET
not used
Controls Notification
Circuit 1
Controls Notification
Circuit 2
Controls
Remote Signalling
Municipal Tie
Controls
Alarm Relay
27