Figure 14: Configuring Annunciators For Sensiscan 2000 - Fire-Lite AFM-16ATX User Manual

Annunciator modules for fire-lite fire alarm control panels
Table of Contents

Advertisement

Figure 14: Configuring Annunciators for Sensiscan 2000

DIP switches must be set before the annunciator will operate properly.
Annunciator Key Switch
(AKS-1) Connector
1. Not Used: This switch must be set "OFF".
2. Expanders Installed:
3. Expanders Installed:
4. Eight-Point Shift: Set switch "ON" to shift the CPU functions from the first eight annunciator
positions to expander positions 57-64.
5. Receive Only: Set this switch "ON" for each annunciator that will provide the same information
as another annunciator in a different location (when two or more annunciators hold the same address,
all but one must be configured as "Receive Only" annunciators).
6. Piezo Disable: Set this switch "ON" to disable the piezo from sounding for any event.
7. Switch Inhibit: To disable the point control switches on the annunciator from executing system
control functions, set this switch "ON." When inhibited, the switches will serve as local Lamp Test
switches only. In addition, the Acknowledge/Lamp Test switch will function only in a local capacity,
unrecognized by the System. Note: For Canadian applications, when annunciator point control
switches are enabled (Switch 7 'OFF'), the AKS-1F or a similar listed enclosure must be employed.
8. Flash Inhibit: Set this switch "ON" to disable the flashing of LEDs associated with unacknow-
ledged events. Flash Inhibit also disables the piezo from sounding.
26
DOWN POSITION = ON
DIP Switch
DIP Switch settings
None
One
Two
OFF
ON
OFF
OFF
OFF
ON
15390 Rev D 8/2/96 P/N 15390:D
:
Three
ON
ON
UP (OPEN) = OFF
DIP Switch