Completing expander connections
Completing installation in a cabinet or an ABF-4F
Plug the two annunciator terminal blocks into the AFM-16ATX or the first AFM-32AX.
Place the annunciator/dress plate assembly into the cabinet or ABF-4F backbox. Secure
the assembly with the screws provided.
secondary (battery backup) power.
Programming and testing the annunciators
This completes annunciator installation. After programming the fire alarm control panel
to accept the annunciators, fully test the Annunciator Control System by ensuring that
each switch performs its intended function, that each LED lights, and that the annuncia-
tors can perform the functions outlined in the section, "Operating the Annunciator."
12
AFM-16ATX/AEM-16ATF
Installation Only
If installing one AFM-16ATX with three
AEM-16ATF expanders in the same dress
plate, perform the following installation
steps:
Connect one end of an expander ribbon
to Connector J2 on the first expander.
Install the second AEM-16ATF expander
in the third dress plate position. Connect
the other end of the expander ribbon
from the first expander to Connector J3
on the second expander.
Connect one end of a ribbon cable to
Connector J2 on the second expander.
Install the third AEM-16ATF expander in
the fourth dress plate position. Connect
the other end of the ribbon cable from the
second expander to Connector J3 on the
third expander.
Apply primary (AC) power, followed by
15390 Rev D 8/2/96 P/N 15390:D