Figure 13: Connecting The Eia-485 Loop - Fire-Lite AFM-16ATX User Manual

Annunciator modules for fire-lite fire alarm control panels
Table of Contents

Advertisement

Annunciators and the Sensiscan 2000
Capabilities
When installed with a Sensiscan 2000, an annunciator can annunciate the status of
initiating and notification circuits, relays, and several system control functions. Each
annunciator LED is automatically assigned to one and only one system point:
Circuits:
* Indication of output circuit activation can be obtained by programming the CPU for
"OUTPUT STATUS."
System
Controls:
System Trouble Indication
Communication between the CPU and the Annunciator Control System is accomplished
over a two-wire EIA-485 serial interface. This communication circuit is supervised by the
FACP.
Loss of communication results in "System Trouble" and "Module Failure"
indications at the FACP CPU.
Installation Requirements
The EIA-485 circuit that drives the annunciator must be connected to the CPU as
illustrated below.

Figure 13: Connecting the EIA-485 Loop

24
Section Six:
IZ-8F, IZ-4F Initiating Device Circuits (alarm and trouble)
IC-4F/ICE-4F Notification Appliance Circuits (trouble)*
CR-4F/CRE-4F Control Relays (trouble)*
TC-2F circuits (trouble)*
TC-4F circuits (trouble)*
Acknowledge
Signal Silence
System Reset
Activate Notification Circuits 1 and 2, the Remote Signalling
Municipal Tie circuit, and the Alarm Relay.
Supervised and Power-limited
EIA-485 (
to AFM TB2 Terminal # 4
15390 Rev D 8/2/96 P/N 15390:D
-
)
(+) EIA-485
to AFM TB2 Terminal # 1