Operating the Annunciators
For a complete description of annunciator operation for various specific applications,
refer to Sensiscan 2000 Manual, Document 15017.

Figure 9: Operating the AFM-16ATX

Local Silence/Acknowledge
16 Annunciator Points
Note 1:
If the annunciator loses communication with the control panel, all the yellow trouble LEDs will
flash.
20
Section Five:
This switch serves two purposes:
Switch
1) When pressed, it first lights all the LEDs on the
AFM-16ATX (except the On Line LED) and then
each expander and also sounds the piezo (pro-
vided it hasn't been disabled) for as long as the
switch is held down.
2) It acknowledges all status changes for both the
annunciator and the expanders. Flashing LEDs
will latch on solid and the piezo will be silenced.
On Line LED
This green indicator flashes during communica-
tion with the control panel.
System Trouble LED
This yellow indicator lights for all trouble condi-
tions in the system (not just for those points or
zones mapped to the annunciator/expanders).
Control Switch
Functions as a local Lamp Test for the two LEDs
dedicated to a point.
Control switches can be used to execute such
system functions as ACKNOWLEDGE, SIGNAL
SILENCE, and SYSTEM RESET. Switches can
also be used to control the states of various output
circuits.
Red LED
Yellow LED