Figure 3: Slide-In Labels - Fire-Lite AFM-16ATX User Manual

Annunciator modules for fire-lite fire alarm control panels
Table of Contents

Advertisement

Figure 4: Terminal Wiring
Do not "T-Tap" the EIA-485 circuit which must
be power-limited. It will not function properly.
Wire as shown below.
Leave the 120-ohm resistor installed across
the EIA-485 Out terminals at the last annun-
ciator on the circuit (see below). Remove this
resistor from all other annunciators.
Connect Earth Ground to a mounting screw
on the backbox or cabinet.
Connect 24 VDC Power to the annunciator.
This power must be power-limited but need
not be supervised by a power supervision
relay since it is inherently supervised by the
control panel (loss of communications is reg-
istered during loss of power to the annuncia-
tor).
Control
Panel
EIA-485 (-)
EIA-485 (+)
Wiring Multiple Annunciators (6000-ft max run)
16

Figure 3: Slide-In Labels

Remove the center pages of this manual. If
using the custom user display labels, type
the appropriate information on the labels.
Carefully cut out the labels and insert them
into the annunciator by slipping them into
the label slots on the back side of the
annunciator face plate.
Note: To ensure the best fit, cut directly
along the dotted line surrounding each la-
bel.
First Annunciator
-
-
TB2
+
+
15390 Rev D 8/2/96 P/N 15390:D
EIA-485 In
( - )
EIA-485 Out ( - )
EIA-485 Out (+)
EIA-485 In
(+)
Common In (-)
Common Out (-)
Power In (+24 VDC)
Power Out (+24 VDC)
Earth Ground
Last Annunciator
-
ELR
-
Part #
+
71244
+
TB2
4
3
2
1
TB1
5
4
3
2
1
TB2