HWS
1500/ME
HWS1500/ME Specifications
ITEMS/UNITS
Voltage Range
Frequency
Power Factor (100/230VAC)(typ) (*1)
Input
Efficiency (100/200VAC)(typ)
Current (100/200VAC)(typ)
Inrush Current (100/200VAC)(typ) (*3)
Leakage Current
Nominal Voltage
Maximum Current (100/200VAC)
Maximum Peak Current
Maximum Power (100/200VAC)
Maximum Peak Power
Maximum Line Regulation
Output
Maximum Load Regulation
Temperature Coefficient
0 to +70
Maximum
Ripple & Noise (*4)
Hold-up Time (typ)
Voltage Adjustable Range
Over Current Protection
Over Voltage Protection
Remote Sensing
Remote ON/OFF Control
Function
Parallel Operation
Series Operation
Monitoring Signal
Line DIP
Operating Temperature
Storage Temperature
Operating Humidity
Environment
Storage Humidity
Vibration
Shock (In package)
Cooling
Withstand Voltage
Isolation
Isolation Resistance
Safety Standards
PFHC
Voltage Fluctuations / Flicker Emissions
Standards
EMI
Immunity
Weight (typ)
Mechanical
Size (W x H x D)
(*1) At Ta=25
and maximum output power.
(*2) For cases where conformance to various safety specs (UL, CSA, EN) are required, input voltage range will be 100 - 240VAC (50/60Hz).
(*3) First in-rush current. Not applicable to the first 0.2ms in-rush current flowing into the power supply noise filter.
(*4) Measure with JEITA RC-9131A probe, Bandwidth of scope :100MHz. (at 100uF electric capacitor and 0.47uF film capacitor on the test fixture board.)
(*5) 85 - 265VAC, constant load.
(*6) No load-Full load, constant input voltage.
(*7) Constant current limit with automatic recovery. Over current condition for more than 5 seconds will cause the
output to shutdown.
Output current exceeding maximum rated output current for more than 10 seconds continuously
will result to output shutdown.
(*8) OVP circuit will shut down output, manual reset (Power cycle) or ON/OFF CNT signal reset.
(*9) At 100/200VAC, nominal output voltage and maximum output current.
(*10) Measured by the each measuring method of UL, EN and CSA (at 60Hz).
When using it as a patient care equipment, all outer surfaces of the equipment shall be
constructed of nonconductive material. See clause 19.5DV.2 of UL60601-1.
(*11) Ratings - Derating at standard mounting.
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
- As for other mountings, refer to derating curve.
(*12) As for UL60601-1, EN60601-1 and CSA-C22.2 No.601.1-M90 (C-UL) basic insulation.
(*13) Peak output current is less than 10 seconds, and duty 35% max. (200VAC Line only)
(Read instruction manual carefully, before using the power supply unit.)
MODEL
HWS1500-24/ME
(*2)
V
(*2) Hz
(*1)
%
(*1)
A
A
(*10) mA
VDC
24
A
65 / 70
(*13)
A
105
W
1560 / 1680
(*13)
W
(*5) mV
96
(*6) mV
144
mVp-p
-10 to 0
mVp-p
(*9) ms
VDC
19.2 - 28.8
(*7)
A
>110.2
(*8) VDC
30.0 - 34.8
(*11)
-10 to +70 ( -10 to +50: 100%, +60: 75%, +70: 50%), start up -20 to 70
%RH
%RH
At no operating, 10 - 55Hz (sweep for 1min.) 19.6m/s² constant, X, Y, Z 1hour each.
Output-FG : 500VAC (300mA), Output-CNT:100VAC (100mA) for 1min.
More than 10M
(*12)
Approved by UL60601-1, EN60601-1, CSA C22.2 No.601.1-M90 (C-UL)
Approved by EN55011 / EN55022-A, FCC-Class A, VCCI-Class A
Built to meet IEC61000-4-2(Level 2,3), -3(Level 3), -4(Level 3),
g
mm
HWS1500-36/ME
AC85 - 265
47 - 63
0.98 / 0.94
84 / 88
19.0 / 10.0
20 / 40
Less than 0.5. (0.2 (typ) at 100VAC / 0.4 (typ) at 230VAC)
36
42 / 46.5
70
1512 / 1674
2520
144
150
Less than 0.02%/
200
240
20
28.8 - 43.2
>73.5
45.0-49.7
Possible
Possible
Possible
Possible
PF (Open collector output)
Built to meet SEMI-F47 (200VAC Line only)
-30 to +85
10 - 90 (No Condensing)
10 - 95 (No Condensing)
Less than 196.1m/s²
Forced air by blower fan
Input - FG : 2kVAC (20mA), Input - Output : 3kVAC (20mA)
More than 100M
Output - FG : 500VDC
Output - CNT : 100VDC at 25
Built to meet IEC61000-3-2
Built to meet IEC61000-3-3
-5(Level 3,4), -6(Level 3), -8(Level 4), -11
3800
126.5 x 82 x 280 (Refer to outline drawing)
HWS1500-48/ME
86 / 90
48
32 / 32
-
1536 / 1536
-
192
288
400
38.4 - 52.8
>33.6
55.2 - 64.8
and 70%RH