Step 3
Step 4
Step 5
Step 6
Step 7

Fan Filter

Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Open the ejector lever downwards to allow extraction of fan assembly.
Pull the front edge of the ejector lever to remove the fan completely.
Insert the new fan assembly in reverse order.
Open the ejector lever upwards to fully seat the new fan assembly.
Refasten the 2 thumbscrews on the fan housing.
Note: Turn on the fan to check if it is inserted correctly.
The fan filter should be replaced after 9000 hours of accumulated use. To replace
the air inlet filter in STRM 5000 NEBS appliance:
Unfasten the 2 thumbscrews on the left of the front access cover.
Open the access door.
Pull out the front edge of the filter from the Velcro backing.
After you separate the filter from the Velcro backing, use your fingers to pull the
filter out of the frame. See

Figure 17 Removing the Fan Tray Filter

Carefully insert a new filter into the chassis front panel as shown in the figure and
push the filter carefully to the left.
Push the filter to reach the end of the front door panel.
After you completely insert the filter, ensure that it is secure against the access
door wall.
STRM 5000 NEBS Hardware Guide
Figure
17.
Fan Filter
33