Custom Energy Savings Settings
12 – TEMPERATURE SETBACK DELAY - HEAT
00-120
(20* factory setting) Select the time delay (in minutes) for which the room
that is in the guest occupancy mode needs to be unoccupied before the temperature
setback is initiated.
This feature prevents initiating temperature setback prematurely while the guest is
still in the room but in an area where occupancy cannot be detected by the occupancy
sensor.
Setting the "Temperature Setback Delay - Heat" to "00", disables the setback in the heat
mode. Set to "00" to disable EMS.
13 – MINIMUM SETBACK TEMPERATURE
52-72 (64°F* factory setting) Select the "Minimum Setback Temperature" in °F.
Setback temperature is calculated by measuring PTAC unit's ability to attain "Recovery
Temperature - Heat" within "Temperature Recovery Time".
If recovery is disabled ("Temperature Recovery Time" is set to "0") or if setback
temperatures have not yet been calculated, the "Minimum Setback Temperature" value
will be used as the setback temperature for heating.
If calculated setback temperature for heating is lower than "Minimum Setback
Temperature", then the "Minimum Setback Temperature" will be used as setback
temperature for heating.
This feature allows defining the minimum temperature in a room when room is
unoccupied and the thermostat is in the setback mode.