Custom Energy Savings Settings
18 – MAXIMUM SETPOINT
60-82 (80°F* factory setting) Select the maximum setpoint in °F that a guest can select.
19 – AUTO CHANGEOVER SETPOINT OFFSET
00-04 (01°F* factory setting) Select the difference between the guest-selected set point and
the heat and cool changeover temperatures.
This value plus the 1st stage differential defined in steps 02 and 04, defines the value
at which the thermostat would automatically change heating/cooling modes.
This feature allows adjustment between heat and cool changeover temperatures to
avoid the system from bouncing back and forth between heating and cooling under
normal operating conditions.
.