The Friedrich RT7 is a nonprogrammable electronic thermostat, which can be used with the following heating/cooling applications:
Note 1: Make the following jumper position changes and Installer Settings for Heat Pump units
System Type | Changeover valve type | Required action |
Heat Pump | B |
|
O |
|
Note 2: The "W2" terminal is used to call for Electric/Auxiliary heat. If your Heat Pump PTAC does not have Electric heat, then the "W2" terminal should not be used and Installer Settings menu 10 (Aux. Stage Offset) should be set to "OFF".
Note 3: For PTAC units with only one fan speed (single "G" fan wire), add a jumper wire to bridge together "GH" and "GL". Connect your fan wire to either terminal after jumper wire has been added.
Note 1: If connecting to a Cool only PTAC unit, the W1 wire terminals will not be used.
Note 2: For PTAC units with only one fan speed (single "G" fan wire), add a jumper wire to bridge together "GH" and "GL". Connect your fan wire to either terminal after jumper wire has been added.
HOW TO ENTER
HOW TO NAVIGATE
HOW TO EXIT
Menu Number | Function Description | Selectable Options | Default setting |
01 | Temperature Scale | F: Fahrenheit C: Celsius | F |
02 | Temperature Calibration | +/- 5.4°F | 0.0°F |
03 | (Not Used) | ||
04 | Max Heat Set Temp | F: 60 to 90 (5°F step) | 80°F |
05 | Min Cool Set Temp | F: 60 to 80 (5°F step) | 65°F |
06 | System Type | H-C: Heat-Cool HP: Heat Pump | H-C |
07 | (Not Used) | ||
08 | (Not Used) | ||
09 | Stage 1 Temperature Control Swing | ±0.25°F ±0.50°F ±1.00°F ±2.25°F | 0.50°F |
10 | Auxiliary Stage Cut-In Offset (only used for HP system type) | OFF (No Electric / Auxiliary heat) -3.0 to -8.0°F (1°F step) | -4.0°F |
11 | (Not Used) | ||
12 | (Not Used) | ||
13 | (Not Used) | ||
14 | (Not Used) | ||
15 | (Not Used) | ||
17 | Always On Backlight | OFF: 10s timeout ON: always ON | OFF |
18 | Reset to default set temperatures after each mode change | ON: uses default temperatures after each mode change (see menu 19 and 20) OFF: Maintain last set temperature for each mode | ON |
19 | Default heat mode set temperature | 60°F to Max Heat Set Temp | 70°F |
20 | Default cool mode set temperature | Min Cool Set Temp to 80°F | 74°F |
98 | Minimum off time - Compressor protection | NO: Immediate off/ on switching YES: 3-minute minimum off time enforced | NO |
99 | Reset | NO: no reset YES: ex-factory reset | NO |
THERMOSTAT SYSTEM MODE SWITCH POSITIONS:
THERMOSTAT FAN SWITCH POSITIONS:
THERMOSTAT BUTTONS:
SETTING A KEYPAD / FRONT PANEL LOCKOUT:
Friedrich Air Conditioning Co.
10001 Reunion Pl Suite 500,
San Antonio, TX 78216 1-877-599-5665
www.friedrich.com
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Friedrich RT7 - Thermostat Installation And Operation Manual