Venting Installation - Superior BRT4036TMN Installation And Operation Instructions Manual

Custom series decorative b-vent fireplace millivolt system
Table of Contents

Advertisement

A B-type venting system must be connected
to the appliance for venting to the outside of
the building.
The following section is provided as a guide
to a standard B-type vent installation.
Standing codes requirements concerning B-
type vent installations may vary within your
state, province or local codes jurisdiction.
Therefore, it is recommended that you check
with your local building codes for specific
requirements or in absence of local codes,
follow Section 7.0 of the current National Fuel
Gas Code ANSI Z223.1/NFPA 54.
This gas appliance must be vented to the
outdoors only and may not be terminated into
an attic space or into a chimney flue servicing
a solid fuel burning appliance.
This appliance may be vented through a
manufactured chimney system or a masonry
chimney using a B-vent adapter or a chim-
ney liner system if all are listed, inspected
and approved by local codes and/or building
authorities.
The examples shown in Figure 10, are
typical of most B-vent installations and codes
practices.
Example 1: Shows the minimum allowable
system height and lateral offset for a 60° or
greater inclination. Code specifies that offsets
at 60° or greater are considered horizontal
and must follow the 75% rule for lateral to
total vertical system height. Codes also allow
only one offset in the total system when at
Listed
Vent Cap
Maintain
Listed
Clearance
60°
8'
Position
Firestop
12' Min.
EXAMPLE 1
10

VENTING INSTALLATION

Maintain
Listed
Clearance
Support Each
Lateral At
Least Every
6 Feet
6'
Position
Firestop
Maintain
Listed
Clearance
Figure 10 - Typical B-Vent Configuration
www.SuperiorFireplaces.US.com
60° or greater. The total vertical height in this
example represents the minimum height of 8
feet and therefore the allowable lateral is 6
feet when the 75% rule applies. If the lateral
length must exceed 75% then the system
must be sized in accordance with Category I
venting tables.
Example 2: Shows a multiple offset each at
45° of inclination. Multiple offsets are permit-
ted if they do not exceed 45° of inclination. The
total lengths of the two offsets are not required
to meet the 75% allowable rule.
Example 3: Shows a single offset at 45° of
inclination and therefore the lateral length at
10 feet of offset does not have to meet the
75% rule.
In each case the offsets must be supported
and firestops must be positioned wherever
the vent must pass through a sub-floor, ceil-
ing joist or an attic overhang. The vent pipe
must terminate vertically into a listed type vent
cap and extend a sufficient height through
an approved roof flashing, roof jack or a roof
thimble (38FST recommended). At all points
listed clearances must be maintained.
Vent terminations must be located in ac-
cordance with height and proximity rules of
NFPA No. 54. These rules apply to vents at
12" diameter or less and require a minimum
height in accordance with the roof pitch and
a minimum of 8 ft. distance from a vertical
wall or obstruction (see Figure 11, page 11).
Listed
Vent Cap
Maintain
Listed
Clearance
45°
12' Min.
Position
Firestop
45°
Maintain
Listed
Clearance
EXAMPLE 2
Listed
Vent Cap
Maintain
Listed
Clearance
45°
10'
Maintain
Listed
Clearance
EXAMPLE 3
126736-01B
12' Min.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents