Nibe F1245 Installer Manual page 67

Ground source
Hide thumbs Also See for F1245:
Table of Contents

Advertisement

Temperature sensor data
Temperature
Resistance
(°C)
(kOhm)
-40
351.0
-35
251.6
-30
182.5
-25
133.8
-20
99.22
-15
74.32
-10
56.20
-5
42.89
0
33.02
5
25.61
10
20.02
15
15.77
20
12.51
25
10.00
30
8.045
35
6.514
40
5.306
45
4.348
50
3.583
55
2.968
60
2.467
65
2.068
70
1.739
75
1.469
80
1.246
85
1.061
90
0.908
95
0.779
100
0.672
Pulling out the cooling module
The cooling module can be pulled out for service and
transport.
Caution
The cooling module is easy to remove if it is
drained first (see page 63).
Weight of the cooling module
Type (kW)
5
6
8
10
12
NIBE™ F1245
Voltage (VDC)
3.256
3.240
3.218
3.189
3.150
3.105
3.047
2.976
2.889
2.789
2.673
2.541
2.399
2.245
2.083
1.916
1.752
1.587
1.426
1.278
1.136
1.007
0.891
0.785
0.691
0.607
0.533
0.469
0.414
Weight (kg)
110
115
125
130
135
NOTE
Shut off the heat pump and turn off the cur-
rent on the safety breaker.
Caution
Remove the front cover according to the de-
scription on page 6.
Close the shut-off valves (QM31), (QM32), (QM33)
1
and (QM34).
Drain the compressor module according to the in-
structions on page 63
F1245
Pull off the lock catches.
2
QM31
3
Disconnect the pipe connection at the shut-off
3
valve (QM31).
Remove the two screws.
4
QM31
QM33
QM34
QM32
2
4
Chapter 9 |
Service
65