Menu 5.9 - floor drying function
length of period 1 - 3, 5-7
Setting range: 0 - 30 days
Default value: 2 days
temp. period 1 - 3, 5-7
Setting range: 15 - 70 °C
Default value:
temp. period 1
temp. period 2
temp. period 3
temp. period 5
temp. period 6
temp. period 7
length of period 4
Setting range: 0 - 30 days
Default value: 3 days
temp. period 4
Setting range: 15 - 70 °C
Default value: 45 °C
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven periods
are to be used, set the remaining period times to 0
days.
Mark the active window to activate the under floor
drying function. A counter at the bottom shows the
number of days the function has been active. The
function counts degree minutes as during normal
heating operation but for the flow temperatures that
are set for the respective period.
NOTE
During floor drying the heating medium pump
in 100% runs regardless of the setting in menu
5.1.10.
TIP
If operating mode "add. heat only" is to be
used, select it in menu 4.2.
For a more even flow temperature the addition
can be started earlier by setting "start for addi-
tion" in menus 4.9.2 to -80. When set under
floor drying periods have stopped, reset the
menus 4.2 and 4.9.2 as per previous settings.
62
Chapter 8 |
Control - Menus
Menu 5.10 - change log
Read off any previous changes to the control system
here.
The date, time and ID no. (unique to certain settings)
and the new set value is shown for every change.
20 °C
30 °C
40 °C
40 °C
30 °C
20 °C
NOTE
The change log is saved at restart and remains
unchanged after factory setting.