Liebert Hisp SE+SC04 Product Documentation page 24

Split air conditioner
Table of Contents

Advertisement

English
Cooling capacities, absorbed power and current, compressor running mode-SE+SC06
model
230 V / 1 Ph / 60 Hz
230 V / 1 Ph / 60 Hz
Indoor conditions: 215C, 50% r.h.
Total cooling capacity
Sensible cooling capacity
Compressor absorbed power
Compressor absorbed current
Indoor conditions: 245C, 50% r.h.
Total cooling capacity
Sensible cooling capacity
Compressor absorbed power
Compressor absorbed current
Indoor conditions: 275C, 47% r.h.
Total cooling capacity
Sensible cooling capacity
Compressor absorbed power
Compressor absorbed current
Indoor conditions: 305C, 40% r.h.
Total cooling capacity
Sensible cooling capacity
Compressor absorbed power
Compressor absorbed current
Max cooling capacities, freecooling mode - SE+SC06 model
230 V / 1 Ph / 60 Hz
Temperatura interna: 21_C
Sensible cooling capacity
Temperatura interna: 24_C
Sensible cooling capacity
Temperatura interna: 27_C
Sensible cooling capacity
Temperatura interna: 30_C
Sensible cooling capacity
Note:
Capacities are quoted for R22 (5 m equivalent distance between SE and SC units). For details of R407C capacities, please contact the
Technical Support Department. Quoted capacities are gross capacities: for net capacities, subtract fan motor heat.
20
25
230 / 1 / 60
230 / 1 / 60
kW
5.6
kW
4.9
kW
1.4
A
5.7
kW
6.1
kW
5.1
kW
1.4
A
5.7
kW
6.4
kW
5.5
kW
1.4
A
5.8
kW
6.7
kW
6.3
kW
1.4
A
5.9
10
230 / 1 / 60
kW
4.3
kW
5.4
kW
6.6
kW
7.8
Outdoor temperature [5C]
30
35
230 / 1 / 60
230 / 1 / 60
5.5
5.3
4.9
4.8
1.5
1.7
6.5
7.3
5.9
5.7
5.0
5.0
1.6
1.7
6.6
7.5
6.3
6.1
5.4
5.3
1.6
1.7
6.7
7.6
6.5
6.3
6.2
6.1
1.6
1.8
6.8
7.6
Outdoor temperature [5C]
15
230 / 1 / 60
2.3
3.5
4.7
5.8
Hisp
40
45
230 / 1 / 60
5.1
4.9
4.7
4.6
1.9
2.1
8.2
9.0
5.5
5.3
4.9
4.9
1.9
2.1
8.3
9.1
5.9
5.7
5.3
5.2
1.9
2.1
8.4
9.2
6.0
5.9
6.0
5.9
1.9
2.1
8.5
9.3
20
230 / 1 / 60
0.4
1.6
2.7
3.9