Cooling capacities, absorbed power and current, compressor running mode-SE+SC08
model
460 V / 3 Ph / 60 Hz
460 V / 3 Ph / 60 Hz
Indoor conditions: 215C, 50% r.h.
Total cooling capacity
Sensible cooling capacity
Compressor absorbed power
Compressor absorbed current
Indoor conditions: 245C, 50% r.h.
Total cooling capacity
Sensible cooling capacity
Compressor absorbed power
Compressor absorbed current
Indoor conditions: 275C, 47% r.h.
Total cooling capacity
Sensible cooling capacity
Compressor absorbed power
Compressor absorbed current
Indoor conditions: 305C, 40% r.h.
Total cooling capacity
Sensible cooling capacity
Compressor absorbed power
Compressor absorbed current
Max cooling capacities, freecooling mode - SE+SC08 model
460 V / 3 Ph / 60 Hz
460 V / 3 Ph / 60 Hz
Temperatura interna: 21_C
Sensible cooling capacity
Temperatura interna: 24_C
Sensible cooling capacity
Temperatura interna: 27_C
Sensible cooling capacity
Temperatura interna: 30_C
Sensible cooling capacity
Note:
Capacities are quoted for R22 (5 m equivalent distance between SE and SC units). For details of R407C capacities, please contact the
Technical Support Department. Quoted capacities are gross capacities: for net capacities, subtract fan motor heat.
24
25
460 / 3 / 60
460 / 3 / 60
kW
6.9
kW
6.9
kW
1.3
A
2.4
kW
7.4
kW
7.4
kW
1.4
A
2.5
kW
8.0
kW
8.0
kW
1.4
A
2.7
kW
8.5
kW
8.5
kW
1.3
A
2.8
10
460 / 3 / 60
kW
8.2
kW
10.4
kW
12.6
kW
14.9
Outdoor temperature [5C]
30
35
460 / 3 / 60
460 / 3 / 60
6.8
6.7
6.8
6.7
1.4
1.6
2.5
2.7
7.3
7.1
7.3
7.1
1.4
1.6
2.6
2.7
7.9
7.7
7.9
7.7
1.5
1.6
2.7
2.8
8.4
8.2
8.4
8.2
1.4
1.6
2.8
2.8
Outdoor temperature [5C]
15
460 / 3 / 60
4.5
6.7
8.9
11.1
Hisp
40
45
460 / 3 / 60
6.5
6.2
6.5
6.2
1.8
2.0
2.9
3.1
6.9
6.7
6.9
6.7
1.8
2.0
2.9
3.1
7.4
7.2
7.4
7.2
1.8
2.0
2.9
3.1
7.9
7.7
7.9
7.7
1.8
2.1
2.9
3.1
20
460 / 3 / 60
0.7
3.0
5.2
7.4

Hide quick links: