; GSD File for the EM 277 PROFIBUS-DP with a DPC31
; MLFB
: 6ES7 277-0AA2.-0XA0
; DATE
: 26-March-2001
;================================================
#Profibus_DP
;General parameters
GSD_Revision
= 1
Vendor_Name
= "Siemens"
Model_Name
= "EM 277 PROFIBUS-DP"
Revision
= "V1.02"
Ident_Number
= 0x089D
Protocol_Ident
= 0
Station_Type
= 0
FMS_supp
= 0
Hardware_Release
= "1.00"
Software_Release
= "1.02"
9.6_supp
= 1
19.2_supp
= 1
45.45_supp
= 1
93.75_supp
= 1
187.5_supp
= 1
500_supp
= 1
1.5M_supp
= 1
3M_supp
= 1
6M_supp
= 1
12M_supp
= 1
MaxTsdr_9.6
= 60
MaxTsdr_19.2
= 60
MaxTsdr_45.45
= 250
MaxTsdr_93.75
= 60
MaxTsdr_187.5
= 60
MaxTsdr_500
= 100
MaxTsdr_1.5M
= 150
MaxTsdr_3M
= 250
MaxTsdr_6M
= 450
MaxTsdr_12M
= 800
Redundancy
= 0
Repeater_Ctrl_Sig
= 2
24V_Pins
= 2
; Slave-Specification:
OrderNumber="6ES7 277-0AA2.-0XA0"
Periphery="SIMATIC S5"
Slave_Family=10@TdF@SIMATIC
Freeze_Mode_supp
= 1
Sync_Mode_supp
= 1
Set_Slave_Add_Supp
= 0
Auto_Baud_supp
= 1
Min_Slave_Intervall
= 1
Fail_Safe
= 0
Max_Diag_Data_Len
= 6
Modul_Offset
= 0
Modular_Station
= 1
Max_Module
= 1
Max_Input_len
= 128
Max_Output_len
= 128
Max_Data_len
= 256
; UserPrmData-Definition
ExtUserPrmData=1 "I/O Offset in the V-memory"
Unsigned16 0 0-10239
EndExtUserPrmData
; UserPrmData: Length and Preset:
User_Prm_Data_Len=3
User_Prm_Data= 0,0,0
Max_User_Prm_Data_Len=3
Ext_User_Prm_Data_Const(0)=0x00,0x00,0x00
Ext_User_Prm_Data_Ref(1)=1
Figure A-31
Listing of the GSD File for the EM 277 PROFIBUS Module
Technical Specifications
;================================================
; Continuation of GSD File
;================================================
; Module Definition List
Module = "2 Bytes Out/ 2 Bytes In
EndModule
Module = "8 Bytes Out/ 8 Bytes In
EndModule
Module = "32 Bytes Out/ 32 Bytes In
0xC0,0x1F,0x1F
EndModule
Module = "64 Bytes Out/ 64 Bytes In
0xC0,0x3F,0x3F
EndModule
Module = "1 Word Out/ 1 Word In
EndModule
Module = "2 Word Out/ 2 Word In
EndModule
Module = "4 Word Out/ 4 Word In
EndModule
Module = "8 Word Out/ 8 Word In
EndModule
Module = "16 Word Out/ 16 Word In
EndModule
Module = "32 Word Out/ 32 Word In
0xC0,0x5F,0x5F
EndModule
Module = "2 Word Out/ 8 Word In
0xC0,0x41,0x47
EndModule
Module = "4 Word Out/ 16 Word In
0xC0,0x43,0x4F
EndModule
Module = "8 Word Out/ 32 Word In
0xC0,0x47,0x5F
EndModule
Module = "8 Word Out/ 2 Word In
0xC0,0x47,0x41
EndModule
Module = "16 Word Out/ 4 Word In
0xC0,0x4F,0x43
EndModule
Module = "32 Word Out/ 8 Word In
0xC0,0x5F,0x47
EndModule
Module = "4 Byte buffer I/O
EndModule
Module = "8 Byte buffer I/O
EndModule
Module = "12 Byte buffer I/O
EndModule
Module = "16 Byte buffer I/O
EndModule
Appendix A
-" 0x31
-" 0x37
-"
-"
-" 0x70
-" 0x71
-" 0x73
-" 0x77
-" 0x7F
-"
-"
-"
-"
-"
-"
-"
-" 0xB3
-" 0xB7
-" 0xBB
-" 0xBF
447