NOTE:
For altitudes over 1000 feet above sea level, adjust range screw (behind end cover). Half turn
max. raises setting 4_ F approx.
Water modulating valve (water cooled units only)— Opening point of condenser water modulating valve
should be set to maintain proper operating pressure in the refrigeration system high side. (see chart on page
16). Closing point of valve should be set low enough to close valve during compressor stand by periods. To
raise, turn counterclockwise, to lower turn clockwise.
NOTE: If any of these checks or adjustments cannot be achieved, refer to Troubleshooting Section of
this manual or call for factory assistance at 1--800--Service.