Assembling The Dc Plug Connectors - SMA SUNNY MINI CENTRAL 6000TL Installation Manual

Pv inverter
Hide thumbs Also See for SUNNY MINI CENTRAL 6000TL:
Table of Contents

Advertisement

SMA Solar Technology AG
5.4.2 Assembling the DC Plug Connectors
In order to connect to the inverter, all connecting cables of the PV modules must be equipped with the
DC plug connectors provided.
To assemble the DC plug connectors, proceed as detailed below. Ensure the plug connectors have
the correct polarity. The DC plug connectors are marked with "+" and " − ".
Cable requirements:
• Use a PV1-F cable.
Procedure
1. Insert the stripped cable into the plug connector as
far as it will go.
2. Press the clamping clip downward until you hear an
audible click.
3. Ensure the cable is correctly in place.
Result
☑ If the conductors are visible in the hollow
cavity of the clamping clip, the cable is in
the correct position.
Installation Guide
Action
• Proceed to step 4.
SMC6-8TL-IEN101040
Electrical Connection
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny mini central 7000tlSunny mini central 8000tl

Table of Contents