Failure Search
Message
Watchdog
Watchdog-Srr
9.3 Red LED is Glowing Continuously
If the red LED of the status display is continuously on during operation, there is either a ground fault
in the PV generator or at least one of the varistors for the overvoltage protection is defective.
9.3.1 Checking the PV Generator for a Ground Fault
1. Disconnect the inverter from both the DC and AC connections as described in section
7.2 "Opening the Inverter" (page 52).
NOTICE!
Excessive voltages can destroy the measuring device.
• Only use measuring devices with a DC input voltage range up to at least 700 V.
2. Measure the voltages between the plus pole of an
individual string and minus pole of an individual
string against the ground potential.
☑ If voltage is found, there is a ground fault in the
corresponding string.
DANGER!
Risk of lethal electric shock.
If a ground fault occurs, the PV generator may carry high voltages.
• Do not touch the frame of the PV generator.
• Wait until no voltage can be measured.
• Do not connect strings with ground faults to the inverter.
68
SMC6-8TL-IEN101040
Description and corrective measure
Internal program run fault.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline