5.5 Connection of the SMA Power Balancer
The Sunny Mini Central is equipped with the SMA Power Balancer as standard. This enables a circuit
connection of 3 Sunny Mini Central to a three-phase feed-in system.
Each of the 3 Sunny Mini Central devices in a group must be connected to a different phase conductor
of the low-voltage grid (L1, L2 and L3)!
By activating this circuit, you can stipulate how the other two Sunny Mini Central devices are to react
if there is a device fault with the third Sunny Mini Central or there is a grid voltage fault in its phase.
Three-phase grid connection
For further information on this subject, see the Technical Information "Three phase
connection with Sunny Mini Central" in the download area at www.SMA.de/en.
The connections for the SMA Power Balancer are galvanically isolated from the rest of the Sunny Mini
Central circuit.
5.5.1 Configuration
The SMA Power Balancer is deactivated at the factory using the "PowerBalancer" parameter
(parameter setting = off) and can only be activated and configured using a communication device.
To change the "PowerBalancer" parameter, you need a personal access code - the so-called SMA
Grid Guard Code. The application form for the personal access code is located in the download area
at www.SMA.de/en, in the "Certificate" category for each inverter.
The configuration options are detailed below.