Minimum Clearances To Combustible Materials - Bixby Energy MaxFire Installation & Operating Manual

Multi-fuel room heater
Hide thumbs Also See for MaxFire:
Table of Contents

Advertisement

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

A
10.5" (267mm)
B
2"
C
12"
NOTE:
Use a non-combustible floor protector under the unit, extending 3" (76mm) past the side of unit
(or less if installed at closer clearances) and 6" (150mm) in front of Room Heater door.
2020866 REV A
C
B
A
Free Standing and Alcove (rear only) Installation Clearances:
(50mm)
(305mm)
Minimum clearances are for temperature concerns and do not allow for enough room
for maintenance. Please allow enough room on the sides for routine maintenance,
6" - 12" (150mm - 305mm) of clearance to non-movable objects (i.e. walls)
is recommended. Also, clearance to the back of the Room Heater is needed for
replacement of the filter.
Alcove Dimensions (Rear Vent Only):
Minimum Height - 42" (1065mm), Minimum Width - 32" (815mm),
Maximum Depth - 24" (610mm)
B
B
B
D
6"
E
3"
B
(150mm)
(75mm)
Floor Protector
E
D