5.
Burner lights up, runs
continuously and emits
visible smoke or shows
excess smoke on
combustion check
6.
Burner lights up, runs
normally but flame cuts
off slowly on shut down
(possibly with smoke or
pulsation)
7.
Burner Pulsates
(a) continuously
BOULTER BUDERUS CAMRAY 5 PAGE 54
7.
Burner pulsates
(a) continuously
(b) at initial firing
8.
Burner locks out on
morning starts then runs
perfectly for rest of day
9.
Burner fails due to blown
fuse.
file://D:\PL47000\PL47000.htm
joints or defective gland
packings)
Motor not driving pump
Check that flexible drive is functioning correctly
shaft
and not slipping.
Blocked atomiser nozzle Remove and replace nozzle.
Oil pressure abnormally
Check oil pressure on gauge and set to the correct
low
pressure (see
Solenoid valve faulty
Break union at outlet to check presence of oil.
Check that seat is clear. Check coil for continuity.
Inspect coil feed wiring to control box.
Pump rotation incorrect Check.
Ignition failure:
Electrodes dirty
Inspect and clean if necessary.
Electrodes mis-set
Inspect and reset gap 3 to 4mm between tips.
2mm in front of nozzle face.
Cracked electrode
Check and replace if cracked or crazed.
insulator.
Electrode leads
Check for proper connections
Air shutter closed
Reset to correct position.
Wrong nozzle
Check make, type and spray angle.
Worn atomiser nozzle
Replace if necessary.
Oversize nozzle fitted in
Check size and replace with correct size of
error
necessary.
Nozzle incorrectly
Replace with correct nozzle.
stamped
Burner air supply
Inspect air intake and fan for fouling of impeller
inadequate
with dirt.
Burner oil pressure
Check pressure and reset to correct pressure (see
excessive
Technical
Air in nozzle
Should self-correct; if air repeatedly present; for
leaks on oil line and flexible.
Magnetic valve not
Inspecting and replace if necessary.
operating correctly
Shut off piston in pump
Replace pump.
sticking
Air shutter setting
Inspect and reset or remove blockage.
incorrect or fan inlet
blocked
Grossly oversized
Checked and replace with correct size and type
nozzle
(see
Air supply inadequate
Check fan operation and cleanliness.
Worn nozzle with
Replace with nozzle of correct type and size (see
excess throughout or
Technical
uneven spray pattern
Air in supply line
Purge at pump to remove.
Blocked flue ways
Clean boiler and flue.
Localised low voltage
Check with local Electricity Board to fit recorder.
supply in early morning
Enlist aid of the Board.
Air present in oil supply Restart burner several times - press lockout reset
button repeat 7(b) above.
Bottom of oil tank
Raise tank or install a two pipe oil supply from tank.
below level of oil pump
Non-return valve faulty
Renew non-return valve. Rectify air leak
or air leak in two pipe
oil supply system.
Short circuit in wiring
Inspect wiring, sheathing and inter-component
connections for broken or damaged leads. Replace
technical
data).
Data).
Technical
Data)
Data).
Page 65 of 67