Commissioning Data - Boulter Camray 5 Installation & Maintenance Manual

Boulter camray 5 oil fired boilers
Table of Contents

Advertisement

BOULTER BUDERUS CAMRAY 5 PAGE 8

3:6 COMMISSIONING DATA

3:6.1 Class C2, Kerosene Oil RIELLO BURNER
Model
Output
Camray5
Utility &
kW Btu/h
System
x1000
11.7
40
40/65
16.1
55
19
65
19
65
65/90A
23.4
80
26.4
90
27.8
95
95/130A
35.2
120
38.1
130
1. There are two columns in the table for combustion gas temperature:-
FLUE EXIT temperature, and
BOILER TEST POINT temperature.
2. Where possible CO2, smoke and flue gas temperatures should be sampled from the FLUE EXIT (i.e.
external balanced flue discharge, or from the test point provided in the conventional flue adaptor)
3. These figures may be used to calculate combustion efficiency.
4. Alternatively (where the forgoing is impractical such as vertical BF) gases can be sampled at the BOILER
TEST POINT inside the casing.
Because the gas temperatures at this point are significantly higher it should not be used to calculate or
measure efficiency.
5. If the BOILER TEST POINT temperature agrees with the data in Table 3:6.1, then use the appropriate
FLUE EXIT temperature from the table to calculate the combustion efficiency.
6. On conventional flue only - flue draught should be measured at the flue exit test point.
Maximum Temperature of Adjustable Controls
Maximum Emissions Limit (Class 1)
Range of Temperature Control
Exit Flue Gas Mass Flow Kg/Sec x 10
file://D:\PL47000\PL47000.htm
Riello
Nozzle
Pump
R D B
Danfoss
Pressure
TYPE
Delevan
BAR psi
US/GPH
ES 7.0
o
0.4x60
484T50 0.5x60
ES 8.0
o
o
ES 7.6
0.6x60
o
ES 7.6
0.6x60
483T50 0.75x60
W 7.2
o
W 8.0
o
0.85x60
o
W 8.0
0.85x60
487T50 1.1x60
o
7.0
W
o
W 7.0
1.25x60
LOW
-3
MID
HIGH
Fuel
C02% Smoke
Rate
No.
Kg/h
100 1.08
10
0-1
115 1.49
11
0-1
110 1.76
12
0-1
110 1.76
10
0-1
105 2.17
11
0-1
115 2.41
12
0-1
115 2.54
11
0-1
100 3.21
12
0-1
100 3.48
12
0-1
40/65
65/90A
Control Stat 85
Limit Stat 110
NOx 250 mg/kWh-CO 125 mg/kWh
Control Stat 0 - 85
6.69
8.46
11.84
9.24
12.79
Page 14 of 67
Flue Exit
Boiler Test
Point Temp
o
Temp
C
o
C
Gross
165-195
215-245
180-225
260-285
180-245
295-320
180
280
200
304
204
335
170
190
190
220
200
230
95/130A
o
o
C +/- 2
C
o
o
C +0/-6
C
o
C
9.61
13.50
17.05
18.49
14/04/2005