TABLE 16: HEAT PUMP WITH ELECTRIC HEAT
Nominal
Heater
Power Supply
2
KW
10
16
26
36
1
Unit with an electric heat accessory will always be wired for a single power supply.
2
Refer to the Heating Capacity table for the actual KW and MBH ratings of each heater at the different voltages.
3
Inverse time circuit breakers may be used in lieu of dual element, time delay fuses.
4
Based on three, insulated copper conductors in steel conduit: 60ºC wire when the total unit ampacity is below 100 amps; 75ºC
wire when the total unit ampacity is 100 amps and above.
18
http://www.rezine.net
1
Heater
FLA
208-3-60
20.8
230-3-60
24.1
460-3-60
12.0
208-3-60
33.4
230-3-60
38.5
460-3-60
19.2
208-3-60
54.2
230-3-60
62.5
460-3-60
31.3
208-3-60
75.1
230-3-60
86.6
460-3-60
43.3
Max, Fuse
Total Unit
Ampacity
AMPS
FA090
31.3
35.1
17.6
46.9
53.1
26.7
73
83.2
41.7
99
113.3
56.7
Page 41
036-21371-001-B-0203
Min. Wire
3
4
Size,
Size,
AMPS
AWG
35
8
40
8
20
12
50
8
60
6
30
10
80
4
90
4
45
8
110
3
125
2
60
6