TABLE 10: STEAM COIL CAPACITIES
UNIT
STEAM COIL
MODEL
MODEL
LA300
1NF0454
LB360
1.
These capacities do not include any blower motor heat.
2.
Multiply these capacities by the factors in Table 11 to correct for higher steam pressure.
TABLE 1 1: CORRECTION FACTORS FOR HIGH STEAM
STEAM PRESSURE (PSIG)
CAPACITY CORRECTION FACTOR
NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH
10
http://www.rezine.net
1
2
, MBH @ 2 PSIG
DRY BULB TEMPERATURE OF AIR ENTERING COIL ( F)
CFM
10
6,000
471
8,000
535
10,000
592
12,000
642
8,000
535
10,000
592
12,000
642
14,000
687
5
10
1.05
1.12
Page 192
036-21335-003-B-0206
30
50
424
380
483
432
535
478
580
518
483
432
535
478
580
518
621
555
15
20
1.19
1.25
70
330
380
422
456
380
422
456
489
25
1.30
Unitary Products Group