York HA090 Technical Manual page 161

Split-system air-cooled condensing units
Table of Contents

Advertisement

036-21096-001-C-0206
SUPPLY AIR BLOWER PERFORMANCE*
RPM
6400
ESP
BHP
KW
600
0.15
1.49
1.42
650
0.31
1.71
1.63
700
0.49
1.95
1.86
750
0.67
2.21
2.10
800
0.85
2.50
2.38
850
1.05
2.80
2.66
900
1.25
3.11
2.96
950
1.46
3.46
3.29
1000
1.67
3.82
3.64
LEU 2 4 0 AIR FLOW PERFORMANCE
2
1.8
1.6
1.4
1.2
1
0.8
0.6
0.4
0.2
0
6400
*When determining required brake horsepower, select nearest HP to the right of selected CFM.
Horsepower ratings on the Airflow Chart are approximate values. To assure correct BHP, please refer to Supply
Air Blower Performance Chart at the top of the page.
4
http://www.rezine.net
7200
ESP
BHP
KW
ESP
-
-
-
-
0.14
2.00
1.90
-
0.32
2.27
2.16
0.12
0.51
2.56
2.44
0.32
0.70
2.85
2.71
0.52
0.91
3.19
3.04
0.74
1.12
3.55
3.38
0.96
1.34
3.92
3.73
1.18
1.56
4.33
4.12
1.42
1000RPM
950RPM
900RPM
850RPM
800RPM
750RPM
700RPM
650RPM
00RPM
2 HP
7200
Cubic Feet Per Minute (CFM)
Page 161
CFM
8000
8800
BHP
KW
ESP
BHP
-
-
-
-
-
-
-
-
2.63
2.50
-
-
2.92
2.78
0.10
3.35
3.25
3.09
0.31
3.70
3.61
3.44
0.53
4.07
3.99
3.80
0.76
4.51
4.43
4.22
1.00
4.97
4.88
4.64
1.24
5.44
4 HP
3 HP
8000
8800
9600
KW
ESP
BHP
KW
-
-
-
-
-
-
-
-
-
-
-
-
3.19
-
-
-
3.52
0.07
4.20
4.00
3.87
0.29
4.62
4.40
4.29
0.53
5.07
4.82
4.73
0.78
5.53
5.26
5.18
-
-
-
5 HP
9600
Unitary Products Group