York HA090 Technical Manual page 39

Split-system air-cooled condensing units
Table of Contents

Advertisement

TABLE 10: PHYSICAL DATA (OUTDOOR UNIT)
1
Compressor
Fans
2
Fan Motors
Coil
Refrigerant-22 (Lbs.)
Unit Weight (Lbs.)
1
These compressors are fully hermetic.
2
These PSC motors are directly connected to the outdoor fans and have inherent protection, ball bearings and a 48 frame. Rotation
(when viewing shaft end of motor) -090 = CW.
3
Includes outdoor unit and matched indoor blower unit, but no piping.
4
Based on a 95 ºF ambient.
TABLE 11: PHYSICAL DATA (INDOOR UNIT)
Coil
Centrifugal Blower (Forward Curve)
1
Blower Motor
Filters (Throwaway)
Refrigerant-22 (Lbs.)
4
Unit Weight
(lbs.)
Accessory Operating Weights (Lbs.)
Shipping Volume (Basic Unit) - cubic feet
1
All of these 1750 RPM motors have a solid base, a 56 frame, a 1.15 service factor, inherent protection & permanently lubricated
ball bearings. Refer to Table 7 for additional motor & drive data.
2
Although every indoor unit is shipped with a small holding charge, this charge will be lost during installation. Loss of all refrigerant
must be reclaimed during installation - NOT vented into the atmosphere. Refer to the above table on the OUTDOOR unit for the
system operating charge.
3
Based on a 80ºF ambient.
4
Refer to Installation Instruction Form 035-18475-000 for the distributed weight of these indoor units.
5
Refer to Table 13 for additional electric heat accessory data.
16
http://www.rezine.net
DESCRIPTION
Rating - tons
Quantity
Diameter - inches No. of Blades
Nominal CFM
HP
RPM
Rows Deep x Rows High
Finned Length - inches
Face Area - square feet
Tube (Copper) OD - inches
Fins (Aluminum) per inch
Holding Charge
3
Operating Charge
4
Pumpdown Capacity
Shipping
Operating
DESCRIPTION
Rows Deep x Rows High
Finned Length - inches
Face Area - square feet
Tube (Copper) OD - inches
Fins (Aluminum) per inch
Diameter x Width - inches
Nominal Rating - HP
Quantity Per Unit - 16" x 25" x 1"
Total Face Area - square feet
2
Holding Charge
3
Pumpdown Capacity
Shipping
Operating
5
Electric Heaters
Supply Air Plenum
Base
Return Air Grille
10 KW
16 KW
26 KW
36 KW
Page 39
036-21371-001-B-0203
UNIT MODEL - EA090
7-1/2
2
24/3
7800
3/4
1100
2 x 36
96
24.00
3/8
16
1.50
18.8
24.6
510
505
UNIT MODEL - FA090
3 x 32
45.5
10.1
3/8
13
15 X 15
1-1/2
4
11.1
-
16.5
425
385
63
66
71
74
102
60
15
45
Unitary Products Group

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents