Product Description
SECTION 1

1.1 Product Features

10
Product Description
The MS-2 is a two zone FACP (Fire Alarm Control Panel) and the MS-4 is a four zone
FACP. The information in this manual refers to both the MS-2 and MS-4 unless
otherwise specified. These control panels provide reliable fire signaling protection for
small to medium sized commercial, industrial and institutional buildings. The FACP is
compatible with System Sensor's I
conventional smoke detectors that can transmit a maintenance trouble signal to the
FACP indicating the need for cleaning and a supervisory 'freeze' signal when the
ambient temperature falls below the detector rating (refer to System Sensor's I
Installation and Maintenance Instructions document I56-1800-00 for device
specifications). In addition, the control panel is compatible with conventional input
devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations,
waterflow devices, tamper switches and other normally-open contact devices. Refer to
Fire•Lite Device Compatibility Document for a complete listing of compatible devices.
Outputs include one NAC (Notification Appliance Circuit) on the MS-2 and two NACs
on the MS-4. Each FACP has a Form-C Alarm and Trouble relay and 24 VDC
resettable power. In addition, the MS-4 has a Form-C Supervisory relay and a
nonresettable power output. The FACP supervises wiring, AC voltage and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating
device will activate audible and visual signaling devices, illuminate an indicating LED,
sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an
optional module used to notify a remote station or initiate a auxiliary control function.
Style B (Class B) IDC (Initiating Device Circuit)
✓ one zone programmable for combination
supervisory and waterflow
✓ MS-2 - two IDCs
✓ MS-4 - four IDCs
Style Y (Class B) NAC (Notification Appliance
Circuit)
✓ MS-2- one NAC
✓ MS-4 - two NACs
Form-C Alarm Relay
Form-C Trouble Relay
Form-C Supervisory Relay (MS-4 only)
3.0 amps total system current standard for MS-2 and MS-4
6.0 amps total system current available for MS-4 with optional second
transformer
Optional Dress Panel DP-MS2/4
Optional Trim Ring P/N: TR-1-R for semi-flush mounting the cabinet
Control Buttons
✓ ACK (Acknowledge)
✓ Alarm Silence
✓ Reset
✓ Walktest
✓ Zone Enable/Disable (one per zone)
detectors which are microprocessor-based
3
MS-2/MS-4 PN 51512:B 08/28/02
Product Features
3
MS-4
ZONE 1
FIRE ALARM
SUPERVISORY
TROUBLE
MAINTENANCE
ZONE 2
FIRE ALARM
SUPERVISORY
TROUBLE
MAINTENANCE
ZONE 3
FIRE ALARM
SUPERVISORY
TROUBLE
MAINTENANCE
ZONE 4
FIRE ALARM
SUPERVISORY
TROUBLE
MAINTENANCE
AC
NAC
ZONE
NAC
SYSTEM
POWER
WALK
ALARM
SILENCE
POWER
DISABLE
DISABLE
FAULT
TROUBLE
TROUBLE
TEST