2.8.9 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
2.8.9.1 ANN-RLY Board Layout
Figure 2.27 illustrates the ANN-RLY board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
2.8.9.2 Specifications
Operating Voltage: 24 VDC
Max. Current:
Relay Contact Ratings:
Operating Temperature: 32
For indoor use in a dry location only
2.8.9.3 Mounting/Installation
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis.
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
ANN-BUS (ID#)
Address DIP switch
Figure 2.27 ANN-RLY Board Layout
Alarm: 75 mA
Standby: 15 mA
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
o
F to 120
ANN-BUS Connector
o
o
o
F (0
C to 49
C)
Installation