Error Mode Detected By Indoor Unit - Toshiba RAV-SM566KRT-E Service Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM566KRT-E:
Table of Contents

Advertisement

Error mode detected by indoor unit

Operation of diagnostic function
Check
Cause of operation
code
No communication from remote
E03
controller (including wireless) and
communication adapter
The serial signal is not output from
outdoor unit to indoor unit.
• Miswiring of inter-unit wire
E04
• Defective serial sending circuit on
outdoor P .C. board
• Defective serial receiving circuit on
indoor P .C. board
E08
Duplicated indoor unit address
Regular communication error between
E18
indoor aster and follower units and
between main and sub units
Coming-off, disconnection or short of
F01
indoor heat exchanger temp. sensor
(TCJ)
Coming-off, disconnection or short of
F02
indoor heat exchanger temp. sensor
(TC)
Coming-off, disconnection or short of
F10
indoor heat exchanger temp. sensor
(TA)
Indoor EEPROM error
F29
• EEPROM access error
L03
Duplicated indoor master unit
There is group wire in individual indoor
L07
unit.
L08
Unset indoor group address
Unset indoor capacity
L09
L30
Abnormal input of outside interlock
P12
Indoor DC fan error
4-way valve system error
P19
• After heating operation has started,
indoor heat exchangers temp. is
down.
Own unit stops while warning is output
P31
to other indoor units.
Status of
Condition
air conditioner
Stop
Displayed when
(Automatic reset)
error is detected
Stop
Displayed when
(Automatic reset)
error is detected
Displayed when
Stop
error is detected
Stop
Displayed when
(Automatic reset)
error is detected
Stop
Displayed when
(Automatic reset)
error is detected
Stop
Displayed when
(Automatic reset)
error is detected
Stop
Displayed when
(Automatic reset)
error is detected
Stop
Displayed when
(Automatic reset)
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Stop
Displayed when
(Automatic reset)
error is detected
Stop
Displayed when
(Follower unit)
error is detected
(Automatic reset)
48
FILE NO. SVM-12004
Judgment and measures
1. Check cables of remote controller and communication adapters.
• Remote controller LCD display OFF (Disconnection)
• Central remote controller [97] check code
1. Outdoor unit does not completely operate.
• Inter-unit wire check, correction of miswiring
• Check outdoor P .C. board. Correct wiring of P .C. board.
2. When outdoor unit normally operates
Check P .C. board (Indoor receiving / Outdoor sending).
1. Check whether remote controller connection (Group/Individual)
was changed or not after power supply turned on
(Finish of group construction/Address check).
∗ If group construction and address are not normal when the
power has been turned on, the mode automatically shifts to
address setup mode. (Resetting of address)
1. Check remote controller wiring.
2. Check indoor power supply wiring.
3. Check indoor P .C. board.
1. Check indoor heat exchanger temp. sensor (TCJ).
2. Check indoor P .C. board.
1. Check indoor heat exchanger temp. sensor (TC).
2. Check indoor P .C. board.
1. Check indoor heat exchanger temp. sensor (TA).
2. Check indoor P .C. board.
1. Check indoor EEPROM. (including socket insertion)
2. Check indoor P .C. board.
1. Check whether remote controller connection (Group/Individual)
was changed or not after power supply turned on
(Finish of group construction/Address check).
∗ If group construction and address are not normal when the
power has been turned on, the mode automatically shifts to
address setup mode. (Resetting of address)
1. Set indoor capacity (DN=11)
1. Check outside devices.
2. Check indoor P .C. board.
1. Position detection error
2. Over-current protective circuit of indoor fan driving unit operated.
3. Indoor fan locked.
4. Check indoor P .C. board.
1. Check 4-way valve.
2. Check 2-way valve and check valve.
3. Check indoor heat exchanger (TC/TCJ).
4. Check indoor P .C. board.
1. Judge follower unit while master unit is [E03], [L03], [L07] or [L08].
2. Check indoor P .C. board.