Function Selection Code No. (Dn) List - Toshiba RAV-SM566KRT-E Service Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM566KRT-E:
Table of Contents

Advertisement

CODE No.
Item
(DN)
01
Filter sign lighting time
02
Filter stain level
03
Central control address
06
Heating suction temp. shift
0C
Preparing indication selection
0F
Cooling-only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
In automatic cooling/heating, temp.
1E
width of cool → heat, heat →
cool mode selection control point
28
Auto restart
Selection of option / error input
2A
(CN80)
Selection of thermostat output
2b
ƒ
(T10
)
2E
Selection of HA (T10
31
Fan (Single operation)
32
Sensor selection
Timer setting
60
(Wired remote controller)
69
Louver setting for cooling
Correction of feeling
86
of strong heating
Power saving
C2
(Current demand X% to
outdoor unit)
Restriction ratio setting for save operation (DODE No. (DN) [C2]) can be set/changed from the normal CODE No. (DN) setup
(Detail CODE No. (DN) setup).

Function selection CODE No. (DN) list

0000: None
0002: 2500H
0004: 10000H
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit
0099: Undecided
0000: No shift
0002: +2°C
0003: +3°C
0000: Preparing indicated
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0001: 4-way air discharge cassette
0004: Concealed duct
0007: Under ceiling
0000: Undecided
0001: No.1 unit
0001: No.1 unit
0000: Individual
0002: Follower unit in group
0000: 0 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000: None
0000: Filter input
0002: External alarm input
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA)

) terminal
0002: Fire alarm input
0000: Impossible
0000: Body TA sensor
0001: Remote controller sensor
0000: Operable
0000: Normal
0000: Not priovided
0050 : 50% to 0100 : 100%
Contents
0001: 150H
0003: 5000H
0005: Clogging sensor used
to
0064: No.64 unit
0001: +1°C
to
0010: +10°C
(Up to +6 is recommended.)
0001: No indication
0008: High wall
0001 to 0034
to
0030: No.30 unit
to
0064: No.64 unit
0001: Master unit in group
to
0010: 10 deg
0001: Provided
0001: Alarm input
(Air cleaner, etc.)
0001: Card input
(Forgotten to be off)
0001: Possible
0001: Operation prohibited
0001: Down allowed
0001: Priovided
69
FILE NO. SVM-12004
At shipment
from factory
0001: 150H
0000: Standard
0099: Undecided
0003: +3°C
0002: +2°C
0000: Preparing indicated
0000: Heat pump
0008: High wall
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
0003: 3 deg
(Ts±1.5)
0000: None
0002: External alarm input
0000: Thermostat ON
0000: Normal
(HA terminal)
0000: Impossible
0000: Body sensor
0000: Operable
0000: Normal
0000: Not priovided
0075 : 75%