Error Mode Detected By Indoor Unit - Toshiba RAV-GM561ATP-E Service Manual

Outdoor unit, digital inverter
Hide thumbs Also See for RAV-GM561ATP-E:
Table of Contents

Advertisement

Error mode detected by indoor unit

Operation of diagnostic function
Check
Cause of errors
code
No communication from remote
E03
controller (including wireless) and
communication adapter
The serial signal is not output from
outdoor unit to indoor unit.
Miswiring of inter-unit wire
Defective serial sending circuit on
E04
outdoor P.C. board
Defective serial receiving circuit on
indoor P.C. board
E08
Duplicated indoor unit address
L03
Duplicated indoor master unit
There is group wire in individual indoor
L07
unit.
L08
Unset indoor group address
L09
Unset indoor capacity
L30
Abnormal input of outside interlock
Float switch operation
P10
Float circuit, Disconnection,
Coming-off, Float switch contact error
P12
Indoor DC fan error
4-way valve system error
After heating operation has started,
P19
indoor heat exchangers temp. is
down.
Own unit stops while warning is output
P31
to other indoor units.
Coming-off, disconnection or short of
F01
indoor heat exchanger temp. sensor
(TCJ)
Coming-off, disconnection or short of
F02
indoor heat exchanger temp. sensor
(TC)
Coming-off, disconnection or short of
F10
indoor heat exchanger temp. sensor
(TA)
Indoor EEPROM error
F29
EEPROM access error
Communication error between indoor
MCU
E10
Communication error between fan
driving MCU and main MCU
Communication error between
E11
Application and indoor unit
Regular communication error between
indoor master and follower units and
E18
between main and sub units
Status of
Condition
air conditioner
Stop
Displayed when
(Automatically
error is detected
reset)
Stop
Displayed when
(Automatically
error is detected
reset)
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Stop
Displayed when
(Automatically
error is detected
reset)
Stop
(Follower unit)
Displayed when
(Automatically
error is detected
reset)
Stop
Displayed when
(Automatically
error is detected
reset)
Stop
Displayed when
(Automatically
error is detected
reset)
Stop
Displayed when
(Automatically
error is detected
reset)
Stop
Displayed when
(Automatically
error is detected
reset)
Stop
Displayed when
(Automatically
error is detected
reset)
Stop
Displayed when
(Automatically
error is detected
reset)
Stop
Displayed when
(Automatically
error is detected
reset)
- 56 -
Judgment and measures
1. Check cables of remote controller and communication adapters.
Remote controller LCD display OFF (Disconnection)
Central remote controller [97] check code
1. Outdoor unit does not completely operate.
Inter-unit wire check, correction of misswiring
Check outdoor P.C. board. Correct wiring of P.C. board.
2. When outdoor unit normally operates
Check P.C. board (Indoor receiving / Outdoor sending).
1. Check whether remote controller connection (Group/Individual)
was changed or not after power supply turned on
(Finish of group construction/Address check).
* If group construction and address are not normal when the
power has been turned on, the mode automatically shifts to
address setup mode. (Resetting of address)
1. Set indoor capacity (CODE No. (DN) = 11)
1. Check outside devices.
2. Check indoor P.C. board.
1. Trouble of drain pump
2. Clogging of drain pump
3. Check float switch.
4.
Check indoor P.C. board.
5. Check Application control kit of indoor unit
1. Position detection error
2. Over-current protective circuit of indoor fan driving unit operated.
3. Indoor fan locked.
4. Check indoor P.C. board.
1. Check 4-way valve.
2. Check PMV
3. Check indoor heat exchanger (TC/TCJ).
4. Check indoor P.C. board.
1. Judge follower unit while header unit is [E03], [L03], [L07] or [L08].
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TCJ).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TC).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TA)
2. Check indoor P.C. board.
1. Check indoor EEPROM. (including socket insertion)
2. Check indoor P.C. board.
1. Check indoor P.C. board.
1. Check power supply / communication harness
2. Check indoor P.C. board
1. Check remote controller wiring.
2. Check indoor power supply wiring.
3. Check indoor P.C. board.
FILE NO. SVM-18043