Replacement Of Service P.c. Board; Requirement When Replacing The Service Indoor P.c. Board Assembly - Toshiba RAV-SM566KRT-E Service Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM566KRT-E:
Table of Contents

Advertisement

9. REPLACEMENT OF SERVICE P.C. BOARD

Model type
RAV-SM∗∗∗ KRT series

[Requirement when replacing the service indoor P.C. board assembly]

In the non-volatile memory (Hereinafter said EEPROM, IC10) installed on the indoor P .C. board before
replacement, the type and capacity code exclusive to the corresponding model have been stored at shipment
from the factory and the important setup data such as refrigerant line /indoor unit /group address in
(AUTO/MANUAL) mode have been stored at installation.
Replace the service indoor P .C. board assembly according to the following procedure.
After replacement, make sure that the indoor unit address is set correctly and also the refrigerant cycle is
working correctly by test operation.
<Replacement procedure>
CASE 1
Before replacement, power of the indoor unit can be turned on and the setup data can be readout
by the wired remote controller.
(If in group operation, reset the power for all indoor units which are connected to the remote controller.)
CASE 2
Before replacement, the setup data can not be read out by the wired remote controller.
Write the data such as "option input selection" setup to EEPROM (see
Read EEPROM data (see
Replace service P.C. board & power ON (see
Write the read data to EEPROM (see
Replace service P.C. board & power ON (see
(According to the customers' information)
P.C. board model
MCC-1510
H1
in Page 61)
ò
H2
ò
H3
in Page 64)
ò
Power reset
H2
ò
ò
Power reset
60
FILE NO. SVM-12004
Label display on P.C. board
04DD 03
in Page 62)
in Page 62)
H3
in Page 64)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents