11-3. Address Setting

When determining indoor unit addresses with wiring completed without piping construction
Wiring example of 2 refrigerant systems
(Solid line: wiring, broken line: refrigerant piping)
O/U
(Power cable only)
I/U
I/U
Refrigerant line
1
1
address
Indoor unit address
1
2
Group address
1
2
For systems like this example, connect
a wired remote controller independently
without connecting remote controller wires,
and then set these addresses.
Group address
Individual: 0000
Header unit: 0001
in case of group control
Follower unit: 0002
SET DATA
SETTING
UNIT No.
R.C.
FILTER
RESET
TEST
SET
CL
8, 5, 2
4,
3, 6, 9
7,
10
11 1
END
Operation procedure
1
2
3
4
8
9
10
O/U
Refrigerant
line address →
(Power cable only)
I/U
I/U
I/U
Indoor unit
1
2
2
address →
3
1
2
2
2
2
Group
address →
CODE No.
No.
ON / OFF
AN
MODE
VE
VENT
SWING/FIX
UNIT LOUVER
5
6
7
11
END
(Manual setting by remote controller)
<Address setting procedure>
• Connect a remote controller to the indoor unit whose
address you want to set one to one.
• Turn ON the power.
1
Push
TEST
,
SET
, and
simultaneously for 4 seconds or more.
2

Set code
3
Set a refrigerant line address with
buttons.
4
Push
SET
Indication on the LCD shows normal
operation.
5
!
Set code
6
Set indoor unit addresses with
tons.
7
SET
Push
Indication on the LCD shows normal
operation.
8
"
Set code
9
Set indoor unit addresses with
as follows:
0000
Individual=
0002
unit=
10
Push
SET
Indication on the LCD shows
normal operation.
11
Push
TEST
.
Indoor unit address setting is completed.
The operation mode returns to normal OFF.