Error Mode Detected By Outdoor Unit - Toshiba RAV-SM566KRT-E Service Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM566KRT-E:
Table of Contents

Advertisement

Error mode detected by outdoor unit

Operation of diagnostic function
Check code
Indoor unit
Cause of operation
High Wall
Disconnection, short of discharge
F04
temp. sensor (TD)
Disconnection, short of outdoor temp.
F06
sensor (TE)
Disconnection, short of outdoor temp.
F07
sensor (TL)
Disconnection, short of outside temp.
F08
sensor (TO)
Disconnection, short of suction temp.
F12
sensor (TS)
Disconnection, short of heat sink temp.
F13
sensor (TH)
Miss-mounting of outdoor temp. sensor
F15
(TE, TS)
F31
Outdoor P.C. EEPROM error
Compressor break down
H01
∗ Although operation has started,
operation frequency decreases and
operation stops.
Compressor lock
H02
∗ Over-current detection after
compressor start-up
H03
Current detection circuit error
Case thermostat operation
H04
∗ Abnormal overheat of compressor
L10
Unset jumper of service P.C. board
Communication error between outdoor
L29
P.C. board MCU
Status of
Condition
air conditioner
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Continue
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Stop
Displayed when
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
Displayed when
Stop
error is detected
50
FILE NO. SVM-12004
Judgment and measures
1. Check discharge temp. sensor (TD).
2. Check outdoor P.C. board.
1. Check temp. sensor (TE).
2. Check outdoor P.C. board.
1. Check temp. sensor (TL).
2. Check outdoor P.C. board.
1. Check outside temp. sensor (TO).
2. Check outdoor P.C. board.
1. Check suction temp. sensor (TS).
2. Check outdoor P.C. board.
1. Check outdoor P.C. board.
1. Check temp. sensor (TE, TS).
2. Check outdoor P.C. board.
1. Check outdoor P.C. board.
1. Check power supply voltage. (AC208V/230V ±10V)
2. Overload operation of refrigerating cycle
1. Trouble of compressor (Lock, etc.):
Replace compressor.
2. Wiring error of compressor (Open phase)
1. Check outdoor P.C. board.
(AC current detection circuit)
1. Check case thermostat and connector.
2. Check gas leak, recharge
3. Check full open of service valve.
4. Check PMV (Pulse Motor Valve).
5. Check broken pipe.
1. Outdoor service P.C. board
Check model type setting jumper wire.
1. Check outdoor P.C. board.

Hide quick links: